2020-09-18
Calculating the connection
wire
In the case of long supply lines for the control circuit, malfunctions may occur on
these supply lines when switching on, due to too high voltage drops.
As a yardstick, the maximum length of the connection wire can be calculated accord-
ing to:
L = 0.004 x U2 x A
Here,
L: Length of connection wire in m
U: Rated supply voltage in V
A: Connector cross-section in mm
2
16
Connector for release voltage E1/E2 of latching
21
Connector for supply voltage A1/A2
24
Electronic controller
25
Cover hood of the electronic controller
Fig. 34
Terminals of the electronic controller
Fig. 35
Optimum cable routing and securing