Description of the individual safety relays
3.6 3TK28 safety relays with relay enabling circuits
3TK28 safety relays
Manual, 07/2016, NEB926157502000/RS-AB/003
35
3.6.2.5
Display of the operating state
Two LEDs and a slide switch indicate the operating state and functioning of the device:
●
DEVICE
●
OUT
Operating state of 3TK2820
LED
Operation
DEVICE
OUT
Line supply
EMERGENCY
STOP
ON
Enabling circuit
On
Not pressed
Pressed
Closed
Pressed
Not pressed
Open
Not pressed
Not pressed
Open
Fault
Fault in sensor circuit
Open
= off
= on
Selector switch
Start
Up
Automatic start
Down
Monitored start