Description of the individual safety relays
3.7 3TK28 safety relays with solid-state enabling circuits
3TK28 safety relays
Manual, 07/2016, NEB926157502000/RS-AB/003
131
3.7.3.7
Technical data 3TK2842
3TK2842-1B...
3TK2842-2B...
EMC emitted interference
IEC 60947-5-1, IEC 60000-4-3,
IEC 60000-4-5, IEC 60000-4-6
Item designation
•
according to DIN 40719 extendable after IEC 204-2
according to IEC 750
KT
•
according to DIN EN 61346-2
F
Number of sensor inputs 1-channel or 2-channel
1
Design of the cascading
cascading or in-service switching
Type of the safety-related wiring of the inputs
single-channel and two-channel
Product feature transverse contact-secure
Yes
Safety Integrity Level (SIL) according to IEC 61508
SIL3
SIL claim limit (for a subsystem) according to EN
62061
3
Safety integrity level (SIL) for delayed release circuit
according to IEC 61508
SIL3
Performance Level (PL)
•
according to ISO 13849-1
e
•
for delayed release circuit according to ISO 13849-1
e
Category
•
according to EN 954-1
4
•
according to ISO 13849-1
4
Safety device type according to IEC 61508-2
Type B
Probability of dangerous failure per hour (PFHD) with
high demand rate according to EN 62061
1/h 0.00000000005
T1 value for proof test interval or service life according
to IEC 61508
a 20
Number of outputs as contact-less semiconductor
switching element
•
for reporting function
–
non-delayed
0
–
delayed switching
0
•
safety-related
–
non-delayed
1
–
delayed switching
1
Stop category according to DIN EN 60204-1
0 + 1