Mounting and Dismantling
3.5 Installing / mounting / removing 3RW5 HMI
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
41
3.5.5
Installing the 3RW5 HMI Standard in the control cabinet door
Requirements
●
Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet
●
3RW5 HMI Standard (accessories)
●
An HMI connecting cable (accessory) of suitable length
●
Cutout of suitable size in the control cabinet door
●
PZ2 screwdriver in installation with door mounting kit IP65
●
Device depth of the 3RW5 HMI Standard:
–
Total depth: 32 mm
–
Embedded depth: 29 mm
●
Permissible wall thickness of the cabinet door:
–
Without IP65 door mounting kit: 1.5 to 3.0 mm
–
With IP65 door mounting kit: 1.0 to 7.0 mm
●
Optional accessories:
–
IP65 door mounting kit
Procedure without door mounting kit IP65
Place the 3RW5 HMI Standard into the cutout of the control cabinet door
①
. Ensure that the
3RW5 HMI Standard engages audibly in 4 fixtures
②
.