3UG463. voltage monitoring relay
10.4 Operation
3UG4 / 3RR2 monitoring relays
278
Manual, 05/2016, NEB927043002000/RS-AC/004
10.4
Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The table below shows the settable parameter information of the 3UG463. voltage
monitoring relays:
Table 10- 2 Parmeter information, 3UG463. voltage monitoring relays with digital setting
Menu
level
Parameters
Setting range
Increment
Factory setting
Minimum value
Maximum value
"RUN"
Threshold for undershoot (U▼)
0.1 V or OFF
1)
10 V or OFF
2)
17 V or OFF
3)
60 V
1)
600 V
2)
275 V
3)
0.1 V
20 V
1)
170 V
2), 3)
"RUN"
Threshold for overshoot (U▲)
0.1 V or OFF
1)
10 V or OFF
2)
17 V or OFF
3)
60 V
1)
600 V
2)
275 V
3)
0.1 V
30 V
1)
260 V
2),3)
"SET"
Hysteresis (Hyst)
0.1 V
30 V
1)
300 V
2)
150 V
3)
0.1 V
2 V
1)
5 V
2), 3)
"SET"
ON-delay time (onDel)
0.1 s
3)
20 s
3)
0.1 s
3)
0.1 s
3)
"SET"
Tripping delay time (
)
0.1 s
20 s
0.1 s
0.1 s
"SET"
Reset response (Mem)
no = Autoreset
yes = Hand-RESET --
no = Autoreset
"SET"
Relay switching behavior
(closed-circuit principle NC /
open-circuit principle NO)
NC
NO
--
NC
1)
3UG4631 voltage monitoring relay
2)
3UG4632 voltage monitoring relay
3)
3UG4633 voltage monitoring relay
Note
The monitoring mode "Overshoot" or "Undershoot" is defined with the setting OFF at the
threshold for undershoot or overshoot.
Note
Deactivating monitoring
If the upper and lower threshold values are deactivated (OFF), monitoring will cease for:
•
Voltage overshoot
•
Voltage undershoot
The up-to-date measured value is displayed permanently.
The parameters are described in Chapter "Parameters (Page 363)."
Menu-based operation is described in Chapter "Menu-based operation (Page 39)."