3PCI SCR Power Controller Series Manual
Introduction
Version 1.2 (19000325)
s
1-3
transformers monitor the true rms current, and feed the information to option CL, which limits the true rms
current regardless of the process control signal.
1.5. Options
Several options are available on the 3PCI. Several of these options are listed below and explained in the
subsections that follow.
•
Three-phase Current Regulation (CR) Option
•
Current Imbalance Detection (CID) Option
•
Lug Kit (LK) Option
•
Extended Ramp (ER) and Fast Ramp (FR) Options.
Most options require current transformers (CTs), which are standard on models rated from 25 A through
225 A. CTs are shipped separately on models rated from 350 A and higher.
1.5.1. Three-phase Current Regulation (CR) Option
The 3-phase Current Regulation (CR) option compares the feedback signal to the control signal, so the line
current will be linear to the control signal, and regulated to maintain a constant current level at the controller
output despite load changes. Current regulation is adjustable from 5% to 125% of the CT rating.
1.5.2. Current Imbalance Detection (CID) Option
The Current Imbalance Detection (CID) option continuously compares the load currents of each phase.
When an imbalance exceeds a pre-determined limit value (5% to 50%), a set of form-C contacts may be
used to alarm and/or turn off the process.
1.5.3. Lug Kit (LK) Option
If required by an application, an optional lug kit (Option LK) is offered. Lug kits are available on 350 A
through 1200 A units. Lugs are provided on 25 A through 225 A units.
1.5.4. Extended Ramp (ER) and Fast Ramp (FR) Options
The increasing rate of the output voltage RMS value is limited to prevent high inrush currents with
transformer-coupled loads or with elements having high cold-to-hot resistance ratios. With a nominal gain
setting, the rate of increase is limited to approximately 100% per second. Additional protective circuits prevent
excessive output bursts due to the fluctuations of re-applied AC source voltage.
The standard ramp time is 1 second. By specifying option ER, the soft-start ramp is increased to 4 seconds.
A fast ramp option (FR) reduces the ramp time to 0.100 seconds (100 ms).
1.6. Technical Specifications
Specifications for the 3PCI SCR Power Controller are given in Table 1-2 and Table 1-1.
Table 1-1. General Technical Specifications
Item Description
Input line voltage
1
208, 240, 400, 480, 600 V
AC
(+10%, -20%) 3-phase
Line frequency
1
50/60 Hz (no circuit change is necessary for either)
Current rating
1
25
A
AC
or 1200 A
AC
per model number (see Table 1-2)
Thermostat contact
rating
120 V
AC
, 5 A, resistive
Input signal
Galvanic isolation:
0-1.5 V (min) 0-15 V (max)
*
Summary of Contents for 3PCI Series
Page 6: ...Table of Contents 3PCI SCR Power Controller Series Manual iv s Version 1 2 19000325 ...
Page 12: ...Introduction 3PCI SCR Power Controller Series Manual 1 6 s Version 1 2 19000325 ...
Page 22: ...Options Setup 3PCI SCR Power Controller Series Manual 4 2 s Version 1 2 19000325 ...
Page 28: ...Troubleshooting 3PCI SCR Power Controller Series Manual 5 6 s Version 1 2 19000325 ...
Page 32: ...Service 3PCI SCR Power Controller Series Manual 6 4 s Version 1 2 19000325 ...
Page 40: ...Addendum 3PCI SCR Power Controller Series Manual A 6 s Version 1 2 19000325 ...
Page 44: ...Index 3PCI SCR Power Controller Series Manual iv s Version 1 2 19000325 ...
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......