Operating the circuit-breaker panel
30
NXAIR M
139-2021.9 / 07
10.2 Position indicators visible on high-voltage door
Circuit-breaker:
CLOSED position or
OPEN position
CLOSED
OPEN
▬
Withdrawable circuit-breaker:
Service position, intermediate position or
test position
Service position
Intermediate position
Test position
Spring state indicator:
CHARGED position or
NOT CHARGED position
CHARGED
NOT CHARGED
▬
Feeder earthing switch:
CLOSED position or
OPEN position
CLOSED
OPEN
▬
10.3 Access to compartments
Regarding accessibility to the individual compartments, NXAIR M switchgear fulfills the loss of service
continuity category LSC 2B according to IEC 62271-200.
The degree of protection between the individual compartments is IP2X in standard design.
The type of accessibility is provided as follows:
Compartment:
Type of accessibility:
Switching-device compartment
Interlock-controlled
Busbar compartment
Tool-based
Connection
compartment
Access from the front side
Interlock-controlled and
tool-based
Access from the rear side
Tool-based
10.4 Opening the high-voltage door
WARNING
Reduced safety
The closed high-voltage door is an important safety element of the switchgear.
The high-voltage door is exclusively opened for performing operational activities
inside the switching-device compartment, such as removing or inserting a
withdrawable circuit-breaker.
Close the high-voltage door:
If an activity inside the switching-device compartment is interrupted.
Immediately after an activity inside the switching-device compartment was
completed.
Before leaving the panel front.