Panels with motor operating mechanism control
139-2021.9 / 07
NXAIR M
213
HINT
Final procedure steps
Next, insert the racking crank for moving the withdrawable circuit-breaker.
Racking the withdrawable circuit-breaker is set to manual operation.
23.5 Selecting electrical operation for racking
NOTICE
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For any local operations ─ manual or electrical ─ set the panel to local
control, for example by switching the local-remote switch to LOCAL
position.
HINT
Electrical racking is only possible when
both
the high-voltage door and the control
door are closed.
After releasing electrical access to the withdrawable circuit-breaker, close
the control door and padlock it.
Fig. 362:
Access mode indicator for racking: starting point “H”