Panels with motor operating mechanism control
139-2021.9 / 07
NXAIR M
209
23.2 Opening the control door
NOTICE
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For any local operations ─ manual or electrical ─ set the panel to local
control, for example by switching the local-remote switch to LOCAL
position.
NOTICE
Maloperation
Electrically racking the withdrawable circuit-breaker is only possible when
both
the high-voltage door and the control door are closed. If the control door is opened
during an electrical racking procedure, the motor stops immediately.
Do not
open the control door during an electrical racking procedure.
Instruction label on control door
In addition to these instructions, an instruction label provided on the control door informs about opening the
control door.
Fig. 353: High-voltage door: instruction label about
opening the control door