H47.FENS037EN-03
03.2021
13/24
Original operating instructions
AEROMAT VT WRG 1000
AERO
11
Commissioning
11.1
Notes on calibration
•
For.units.with.CO
2
sensors or CO
2
.and.TVOC.sensors,.
a.one-off.calibration.of.the.sensors.is.performed.
during.the.commissioning..The.sensors.adapt.to.the.
environment.
•
The.room.temperature.must.be.between.4.°C.and.
50.°C.
•
The.calibration.lasts.24.hours.
•
The.automatic.mode.already.functions.during.the.
calibration.
• AEROMAT VT WRG 1000
.smart:.the.air.quality.
is.already.displayed.during.the.calibration.in.the.
SIEGENIA.Comfort.app.
•
The.accuracy.of.the.sensor.rises.with.the.continuing.
duration.of.the.calibration.
11.2
Performance of calibration
1.
Air.the.room.thoroughly.for.10.min.
2.
Switch.
AEROMAT VT WRG 1000
.to.the.electricity.
grid.
3.
The.exhaust.air.sensors.automatically.start.a.
warming-up.phase.(duration.approx..5.min.):
2.LEDs.flash.red
membrane.key.flashes.blue
4.
The.calibration.starts.automatically.