Siebert C9302-YE Operating Instructions Manual Download Page 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
C9302-YE 

Control computer for XC-Boards

®

 

with EtherNet/IP interface 

Operating instructions

 

 

 

 

Summary of Contents for C9302-YE

Page 1: ...C9302 YE Control computer for XC Boards with EtherNet IP interface Operating instructions ...

Page 2: ...rl 4 rue de l Abbé Louis Verdet F 57200 Sarreguemines P O Box 90 334 F 57203 Sarreguemines Cédex Phone 33 0 3 87 98 63 68 Fax 33 0 3 87 98 63 94 email info fr siebert group com ITALY Siebert Italia Srl Via Galileo Galilei 2A I 39100 Bolzano BZ Phone 39 0 471 053753 Fax 39 0 471 053754 email info it siebert group com THE NETHERLANDS Siebert Nederland B V Jadedreef 26 NL 7828 BH Emmen Phone 31 0 591...

Page 3: ...rd are registered trademarks of Siebert Industrieelektronik GmbH All other product names mentioned herein may be trademarks or registered trademarks of their respective owners We reserve the right to make alterations to the technical data and delivery options without notice All rights reserved including the rights of translation No part of this document may in any form or by any means print photoc...

Page 4: ...format 8 6 IP settings 8 7 Data format 10 8 Messages on the display 11 9 Setting the display type via Properties 12 Number to be displayed Raw Value 12 Decimal points Decimal Dots 12 Offset scale factor multiplier and divisor 12 Threshold values Range 13 Flags 13 Attributes for flashing and blinking modes 13 Format 13 10 Flashing modes and display attributes 14 11 Flags 15 12 Setting the basic bri...

Page 5: ...ded for use in industrial environments They may only be operated within the limit values stipulated by the technical data When configuring installing maintaining and testing the units the safety and accident prevention regulations relevant to use in each individual case must be complied with Trouble free safe operation of the units requires proper transport storage installation mounting and carefu...

Page 6: ...o to be kept short due to any interference which might be emitted by the shielding Neither excessively long cables nor cable loops may be placed inside the units The connection of the cable shielding to the functional ground PE must be as short and low impedance as possible It should be made directly to the mounting plate over a large area with a conductive clip mounting plate conductive clamp dat...

Page 7: ... display panels Anzeigefeld H1 Anzeigefeld H2 Anzeigefeld H3 Anzeigefeld H4 39026 240 247 856 Total Soll Ist Trend The electrical design of the XC Boards is documented in the function chart supplied The following figure shows the basic structure of the XC Boards Data telegrams sent to the display are valid for either a specific display field or for all display fields see chapter Data format Target...

Page 8: ...68 20 250 Subnet mask 255 255 255 0 Gateway 0 0 0 0 DHCP Off The values can be changed in an engineering framework for example Rockwell Studio 5000 Alternatively you can change the IP settings using the program EtherNet IP Tool You find the program on the data carrier included in delivery as a ZIP archive file or on www siebert group com After unpacking this file the program EthernetIPTool exe can...

Page 9: ... click the OK button After successful configuration the following window opens After that the display carries out a restart and can be accesses via the new IP settings The windows is closed by clicking OK once and a new search for EtherNet IP devices starts ...

Page 10: ...ter Setting the display type via Properties The basic brightness of all display fields can be set with the value 0 16 00xx as high byte of the property see chapter Setting of the basic brightness Example 1 The decimal number 15 has to be shown on the display field H1 As Property 16 0100 and as Value 16 0000_000F has to be send Because EtherNet IP uses the byte order little endian the bytes are sen...

Page 11: ...module not configured or scanner in idle state on red error restart required blinking red error restart required If connection fails or problems occur during operation the display shows error Possible causes are IP problems caused by wrong network parameters multiple assigned device names commanding of not defined properties or other fieldbus faults Once the connection has been established the fol...

Page 12: ... mask For example multiple decimal points can be used to display a date or codes A set bit corresponds with a set decimal point The least significant bit corresponds to the decimal point of the least significant digit If for example the number 1234 is to be displayed with a decimal point between the 100th and the 10th digit the bit mask must be set to the value 0x04 and 12 34 appears on the displa...

Page 13: ... are set See chapter flags Attributes for flashing and blinking modes property numbers 7 16 07 and 9 16 09 This initialization values define the blinking modes for the standard display property number 7 16 07 and the Out of range display property number 9 16 09 See chapter flashing modes Format property numbers 10 16 0A and 11 16 0B These two initialization parameters define the alignment of the d...

Page 14: ...033 Slow flashing 15 16 0000_000F Short darkening 63 16 0000_003F Low beaming 27 16 0000_001B High beaming 228 16 0000_00E4 In the case of displays with multicolor LEDs red and green the attribute for the red color is set with the least significant byte and the attribute for the green color with the next higher byte The meaning of the bytes for red and green is identical With the same attributes f...

Page 15: ...pletely when the value exceeds the maximum display capacity Invalid initial value If the value sent to the display is invalid is shown on each position Overflow If the value sent to the display is that large that it cannot be displayed on the display is shown on each position on the upper segments If the overflow function is deactivated the value that can be displayed as large as possible is displ...

Page 16: ... darkness the decimal point of the least significant decade of the display field H1 flashes Example1 the standard luminosity has to be changed to 10 As Property 16 0002 and as Value 16 0000_000A has to be send Because EtherNet IP uses the byte order little endian the bytes are sent as follows 16 bit Property 32 bit signed number QW0 16 0002 QD1 16 0000_000A equals with the decimal number 10 QB0 QB...

Page 17: ...302 EIP 1 11 17 17 Technische 13 Technical data Fieldbus Interface EtherNet IP MAC address The MAC address for the field bus coupling can be found on the control computer of the device Integrated switch Yes ...