General Information Regarding the Wiring
Standardized cross-sections of round conductors:
AWG/MCM
ISO cross-section [mm²]
Value
Equivalent cross-section [mm²]
0.2
24
0.205
–
22
0.324
0.5
20
0.519
0.75
18
0.82
1.0
–
–
1.5
16
1.3
2.5
14
2.1
4.0
12
3.3
6.0
10
5.3
10
8
8.4
16
6
13.3
25
4
21.2
35
2
33.6
50
0
53.5
70
00
67.4
95
000
85.0
–
0000
107.2
120
250 MCM
127
150
300 MCM
152
185
350 MCM
177
240
500 MCM
253
300
600 MCM
304
Note
The line corresponds to a value when the connection possibilities are taken into account.
9.1.1
Motor Cable
DANGER
Dangerous shock currents
connect the motor housing to the ground of the machine or
connect the ground terminal of the motor connector to the central ground
point of the machine.
→ Consider the following with regard to shielding: Always use shielded
motor cables.
54