11
Technical data
11.1
Data sheet
Table 15: Features
Features
Sensor principle
Transponder
Coding
Uniquely coded
Locking force F
max
With straight TR110-XAS actuator
3,900 N (EN ISO 14119)
With angled TR110-XABT actuator
1,500 N (EN ISO 14119)
With TR110-XAFx hinged actuator
2,600 N (EN ISO 14119)
Retaining force F
Zh
(F
Zh
= F
max
/1.3)
With straight TR110-XAS actuator
300 N (EN ISO 14119)
With angled TR110-XABT actuator
1,100 N (EN ISO 14119)
With TR110-XAFx hinged actuator
2,000 N (EN ISO 14119)
Actuating force
10 N
Retaining force
20 N
Force against which unlocking is possible
≤
20 N
Actuating frequency
≤
0.5 Hz
Starting speed
≤
20 m/min
Overrun
5 mm
Table 16: Safety-related parameters
Safety-related parameters
Performance level
1)
PL e (EN ISO 13849-1)
Category
1)
4 (EN ISO 13849-1)
PFHd
2)
(mean probability of a dangerous fail‐
ure per hour)
4.1 × 10
–9
T
M
(mission time)
20 years (EN ISO 13849–1)
Type
Type 4 (EN ISO 14119)
Coding level
High coding level (EN ISO 14119)
Safe status when a fault occurs
At least one safety-related semiconductor out‐
put (OSSD) is in the OFF state.
1)
Applies to monitoring the door position (interlocking monitoring) and locking monitoring.
2)
The locking solenoid is externally controlled and so does not contribute to the probability of failure. The
safety level of the locking device controller is determined exclusively by the external controller.
Table 17: Electrical data
Electrical data
Classification based on cULus
Class 2
Protection class
III (IEC 61140)
Utilization category
DC-13: 24 V, 150 mA (IEC 60947-5-2)
Supply voltage U
V
Safety switches
Locking solenoid
1)
20.4 V DC … 27.6 V DC
20.4 V DC … 26.4 V DC
Current consumption
TECHNICAL DATA
11
8023119/15LY/2019-10-28 | SICK
O P E R A T I N G I N S T R U C T I O N S | TR110 Lock
45