COMMISSIONING AND CONFIGURATION
8022483/108R/2018-07-09 | SICK
SAFETY-RELATED 2D LIDAR SENSOR | TIM361S
23
Subject to change without notice
5.4.3
Display of the current operational status
The "Monitor field analysis" page (in the navigation area of the device window, below
the "monitor" node) displays the current operational status consisting of measurement
data, status of the individual fields as well as status of the switching inputs and
outputs.
The field monitor, which is placed in the middle of the page, displays measurement
data as blue points and/or a blue line. Penetrated fields are shown in yellow; free fields
appear in green.
5.4.4
Changing parameters
DANGER
Risk of injury/risk of damage due to incorrect parameters!
Parameter changes are transferred to the device and take effect immediately
after being edited. Permanent saving (in the non-volatile memory of the device)
does not occur, however, until the "Save permanently" button is clicked.
After parameter changes, the effectiveness of the protective device in the
application must be reviewed and documented.
Before beginning configuration ensure that the machine, plant or application in
which the TiM361S is involved as part of a safety function is in a safe state.
Please note:
The individual parameters of the device can be changed on the pages below the
"Parameters" node in the navigation area.
The TiM361S must be configured using the SOPAS configuration software.
5.4.5
Default configuration
The product is delivered with the following default configuration, which prevents
unintentional or unaware sensor activation.
DANGER
Risk of ineffectiveness of the protective device
After configuring the product or after making parameter changes, the
effectiveness of the protective device in the application must be reviewed and
documented.
For a safety-related use of the TiM361S, the configuration and commissioning must
only be performed by appropriately qualified personnel (see also Qualification).