![SICK STR1 Operating Instructions Manual Download Page 41](http://html1.mh-extra.com/html/sick/str1/str1_operating-instructions-manual_1264703041.webp)
Alignment of sensor and actuator
Assured switch-
on distance S
ao
Assured switch
off distance S
ar
Minimum dis‐
tance with paral‐
lel approach
≤
3 mm
≤
6 mm
1)
≥
15 mm
–
1)
Only applies in limited temperature range of –10 °C … +70 °C. Devices with serial number 1824*** or
lower only support the limited temperature range. The serial number is displayed on the safety switch
over the data matrix code.
Sensing ranges for “Flat” actuator
Table 27: Sensing ranges for “Flat” actuator
Alignment of sensor and actuator
Assured switch-
on distance S
ao
Assured switch
off distance S
ar
Minimum dis‐
tance with paral‐
lel approach
≤
10 mm
≤
14 mm
1)
≥
28 mm
8 mm
≤
4 mm
≤
6 mm
1)
≥
28 mm
5 mm
≤
3 mm
≤
9 mm
1)
≥
20 mm
4 mm
Not possible
1)
Only applies in limited temperature range of –10 °C … +70 °C. Devices with serial number 1824*** or
lower only support the limited temperature range. The serial number is displayed on the safety switch
over the data matrix code.
TECHNICAL DATA
11
8018754/12IU/2020-01-30 | SICK
O P E R A T I N G I N S T R U C T I O N S | STR1
41
Subject to change without notice