7 INSTALLATION AND USE PROCEDURES
7.2.3
Define the area to be monitored
WARNING
The system is disabled during configuration. Prepare opportune safety measures in the
dangerous area protected by the system before configuring the system.
1. In the safeRS3 Designer application click
Configuration
.
2. Add the desired number of sensors in the plane.
3. Define the position and inclination of each sensor.
4. Define the selected safety working modes, the detection distance, the angular
coverage and the restart timeout for each protective field of each sensor.
7.2.4
Configure the inputs and outputs
1. In the safeRS3 Designer application, click
Settings
.
2. Click
Digital Input-Output
and define the input and output functions.
3. If the muting is managed, click
Muting
and assign the sensors to the groups
according to the logic of the digital inputs.
4. Click
APPLY CHANGES
to save the configuration.