5.9.4
Enable muting signal characteristics
The muting function is enabled only if both logic signals of the dedicated input meet
certain characteristics.
Below is a graphic representation of the signal characteristics.
In the
safeRS3 Designer
application, in
Settings
>
Digital Input-Output
it is necessary
to set the parameters that define the signal characteristics.
Note
: with pulse duration = 0, it is sufficient that the input signals are at high logic level
(1) to enable muting.
5.9.5
Muting status
Any output dedicated to the muting status (Muting enable feedback signal) is activated
if at least one of the groups of sensors is in muting.
NOTICE
It is the responsibility of the machinery manufacturer to assess whether the indication
of the muting status is necessary (as defined in section 5.2.5 of EN ISO 13849-1:2015
standard).
5.10
Anti-tampering functions: anti-rotation around axes
5.10.1
Anti-rotation around axes
The sensor detects rotation around its axes.
5 FUNCTIONING PRINCIPLES
8027489/2022-03-01 | SICK
Subject to change without notice
O P E R A T I N G I N S T R U C T I O N S | safeRS3