116
O P E R A T I N G I N S T R U C T I O N S | safeRS3
8027489/2022-03-01 | SICK
Subject to change without notice
9 TECHNICAL REFERENCES
9.5.3
Restart signal
Part
Description
Detection signal 1
Detection signal 2
The Detection signal 1 and Detection signal 2 outputs go to ON-state as
soon as the last channel has correctly completed the transition 0 -> 1 -> 0.
Restart signal CH1
Restart signal CH2
Interchangeable channel. Both channels of Restart signal must have a
transition of logical level 0 -> 1 ->0. The time they stay at high logical level
(t) must be at least 200 ms.
Dt
Activation delay. Less than 50 ms.
Diff
Less than 100 ms. If the value is greater than 100 ms, the system
maintains the outputs deactivated.
9.5.4
Active dynamic configuration
With one input