5

After the protective device is released and the muting function ends, the request of the
muting function must end after a defined time (max. 10 s, fixed value).

1

1

2

4

3

MR

TE

ESPE

OSSDs

Muting

active

t

Figure 13: Correct sequence for muting function with ending by higher-level control

1

Monitoring of the complementary circuit

2

Interruption of the protective device is expected after a defined time (max. 4 s, depending
on the speed of the conveyor). The muting function starts when the protective device is
interrupted.

3

Maximum duration of muting function is defined (depending on the length of the material
and the speed of the conveyor).

4

Ending of the muting function after the protective device is released and a defined delay
time has gone by (max. 4 s, depending on the speed of the conveyor).

After the higher-level control has requested ending the muting function, the protective
device must be released within a defined delay time (max. 4 s, depending on the speed of
the conveyor). Once this delay time has elapsed, the muting function is ended.

11.3

Time Extension Function

Once the muting function is active after a correct initiation sequence, the Time Exten‐
sion (TE) signal can be used to extend the maximum duration of the muting function.

This function can be necessary in the following situations:

The conveyor must stop while the muting function is active.

The materials being transported on the conveyor are placed directly one behind
the other at a distance of less than 200 mm or at the distances specified in the
risk assessment.

To activate this function, the Time Extension (TE) signal must be set to HIGH during a
correctly initiated muting function. The signal must remain on HIGH while the protective
field of the Type 4 electro-sensitive protective device is interrupted. Changing to LOW for
a period longer than T

Clearance

 ends the time extension.

To prevent a sequencing error, the Time Extension (TE) must end before the muting
function request ends or before the muting function is ended due to the release of the
electro-sensitive protective function.

The Time Extension function is limited to a maximum duration of 100 h pro muting
process.

OPERATION 

11

8021675/ZV26/2019-05-13 | SICK

O P E R A T I N G   I N S T R U C T I O N S | Safe Entry Exit

41

Subject to change without notice

Summary of Contents for Safe Entry Exit

Page 1: ...O P E R A T I N G I N S T R U C T I O N S Safe Entry Exit Safety System...

Page 2: ...ble within the limits of the legal determination of Copyright Law Any modifica tion abridgment or translation of this document is prohibited without the express writ ten permission of SICK AG The trad...

Page 3: ...ements for the electro sensitive protective device 13 3 5 Construction and function 14 3 6 Limits of the safety system 14 3 7 Functions 15 4 Project planning 16 4 1 Manufacturer of the machine 16 4 1...

Page 4: ...tion 29 7 6 1 Configuration of Sequence monitoring 29 7 6 2 Configuration of Time monitoring 31 7 6 3 Configuration of PLC monitoring override 35 8 Commissioning 37 8 1 Safety 37 8 2 Thorough check 37...

Page 5: ...Annex 48 15 1 Checklist for initial commissioning and commissioning 48 CONTENTS 8021675 ZV26 2019 05 13 SICK O P E R A T I N G I N S T R U C T I O N S Safe Entry Exit 5 Subject to change without noti...

Page 6: ...information about the possible components of the Safe Entry Exit Table 1 Available documents Document type Title Part number Operating instructions Flexi Soft Modular Safety Controller Hardware 801299...

Page 7: ...are organized by the life phases of the safety system project planning mounting electrical installation commissioning operation and main tenance 1 4 Symbols and document conventions The following symb...

Page 8: ...instructions and mounting instructions of SICK components suitable for the safety system The Flexi Soft Designer configuration software Other configuration tools e g Excel tool Pre configured project...

Page 9: ...r into the hazardous area The conveyor moves at a defined speed maximum of 4 different speeds during the transportation of the material The material is at least 500 mm long The length of the material...

Page 10: ...trol and the Type 4 electro sensitive protective device is interrupted When the muting function is inactive the Type 4 electro sensitive protective device detects an object The voltage supply of the h...

Page 11: ...re Flexi Soft safety controller main module Flexi Soft safety controller expansion module I O module 8 inputs 4 outputs Optional if the conveyor is going to switch between different speeds Flexi Soft...

Page 12: ...tion of the pushbutton there must be a complete view of the hazardous area Activating the pushbutton must not initiate any movement of the machine The reset pushbutton must be designed in accordance w...

Page 13: ...vel control and signal source must also correspond to PL e and have a MTTFd value of at least 100 a Measures must be taken with regard to the voltage supply for the higher level control so as to preve...

Page 14: ...stop While the material is passing through the opening the safety controller continues to monitor the signals from the Type 4 electro sensitive protective device If the actual duration of the interrup...

Page 15: ...necessary switches to the safe state see Muting function page 40 Time Extension Function After a correct initiation sequence of the muting function the maximum dura tion of the muting function can be...

Page 16: ...has the following duties b Executing a risk assessment b Verifying and validating the safety functions b Integrating the individual components in accordance with the appropriate stan dards b Please n...

Page 17: ...le The protective device is then not actuated during material trans port however people are still detected 4 4 Design This chapter contains information about implementing the design of the safety syst...

Page 18: ...e risk assessment must determine to what degree people can misuse a process sig nal intended for transport goods in order to activate the muting function themselves by interrupting the Type 4 electro...

Page 19: ...device If the risk assessment concludes that persons in front of the material definitely need more than 200 mm the distance can be adjusted accordingly 4 4 5 Calculating response times and stopping t...

Page 20: ...Type 4 The electro sensitive protective device must conform to Type 4 and can be a safety light curtain for example Independent Control Sys tem The signals of the higher level control are part of the...

Page 21: ...sessment Determination of the thorough checks must be documented in a traceable manner A thorough check must be carried out during commissioning and following modifi cations The regular thorough check...

Page 22: ...nts 5 1 Mounting conditions for the electro sensitive protective device For mounting conditions see Type 4 electro sensitive protective device page 17 5 MOUNTING 22 O P E R A T I N G I N S T R U C T I...

Page 23: ...nst overvoltage overcurrent etc according to the manufacturer s instructions for the individual components Mechanical fastening of the wiring of the pushbutton for the manual muting device e g with ca...

Page 24: ...f timings need to be set for different con veyor speeds or different material sizes Table 6 Function of the connections Connection Function l1 S301 1 Timing 1 l2 S301 2 Timing 2 l3 S301 3 Timing 3 l4...

Page 25: ...hese signals must be coded as 1 of n For more information see 1 of n timing sets page 43 Up to four timing sets can be configured and selected accordingly via signals The fol lowing table describes th...

Page 26: ...is corresponds to the hardware configuration and logic of the project file with an activated Timing Set Selection function but it can be imported into any Flexi Soft CPU module firmware version 4 00 C...

Page 27: ...rent timing sets can be selected sequentially using the Timing Set Selec tion function In the project file with a deactivated Timing Set Selection function Timing Set 1 is selected as standard Assumed...

Page 28: ...n blocks with inputs and outputs Links connect these elements Links are represented as lines Every element contains blue anchor points which represent the inputs and outputs of the elements A link can...

Page 29: ...ride All user defined function blocks in the safety related application software are locked and do not have to be configured Data relating to the speed of the conveyor and the size of the material bei...

Page 30: ...iation is safety related If the risk assessment concludes that people in front of the material definitely need more than 200 mm of space the distance can be adjusted accordingly Termination network Fi...

Page 31: ...sures that people located between or behind the material being transported will be detected The calculation of Tclearance and Ttermination is safety related 7 6 2 Configuration of Time monitoring Time...

Page 32: ...for the following two networks the cycle time of this Clock generator function block is referred to as Tclock period We recommend setting the cycle time to around 100 ms Min time monitoring network F...

Page 33: ...function block is reached with the pre set clock determines the minimum duration of the muting function The minimum duration of the muting function is calculated using the following formula The mater...

Page 34: ...ed on the counting of peri ods in a defined clock with a defined overflow value The defined clock periods are set in the Time monitoring general network see Configura tion of Time monitoring page 31 T...

Page 35: ...ulated minimum duration the safety sys tem goes into the error state 7 6 3 Configuration of PLC monitoring override Timing Set Selection Monitoring network Figure 9 Timing Set Selection Monitoring net...

Page 36: ...l pathways when the function is used with 2 timing sets In this case the signals must be connected to the input with the same numbering pro ceeding in sequence All remaining inputs of the operating mo...

Page 37: ...unting or the electrical connection After exceptional events such as after a manipulation has been detected after modification of the machine or after replacing components The thorough check ensures t...

Page 38: ...NOTE Information is included in the operating instructions for the components 9 MAINTENANCE 38 O P E R A T I N G I N S T R U C T I O N S Safe Entry Exit 8021675 ZV26 2019 05 13 SICK Subject to change...

Page 39: ...on delay timer Logic execution time 20 ms Activate the Logic execution time optimization option in Flexi Soft Designer Deactivate unnecessary functions e g Flexi Loop For more information see chapter...

Page 40: ...ivate the muting function If the safety controller detects a deviation in sequence or timing the safe state is activated The only exception is if the protective field of the Type 4 electro sensitive p...

Page 41: ...11 3 Time Extension Function Once the muting function is active after a correct initiation sequence the Time Exten sion TE signal can be used to extend the maximum duration of the muting function This...

Page 42: ...material is interrupting the protective field of the Type 4 electro sensitive protective device This function can be activated exclusively by activating a spring back pushbutton Requirements for the...

Page 43: ...ing function It allows the muting function to be set for different conveyor speeds and different material lengths This function is configured via timing sets that contain a value for every configured...

Page 44: ...3849 1 PFHd mean probability of one dan gerous failure per hour 5 34 10 7 Supply voltage UV 24 V DC 16 8 V DC 28 8 V DC SELV 1 Ambient operating temperature See operating instructions for the individu...

Page 45: ...Type 4 electro sensitive protective device used Table 17 Safe Entry Exit ordering data Type 4 electro sensitive protective device from SICK Product page deTec4 Prime www sick com deTec4_Prime deTec4...

Page 46: ...lowing components are not included in the scope of delivery They must be selected as appropriate for the application and ordered separately Table 18 Safe Entry Exit ordering data Description Type code...

Page 47: ...ety controller main module FX3 CPU000000 1043783 Flexi Soft safety controller expansion module I O module 8 inputs 4 outputs FX3 XTIO84002 1044125 Flexi Soft safety controller system plug FX3 MPL00000...

Page 48: ...es No 1 4 Are functions of the Type 4 elec tro sensitive protective device that affect the direct correlation between the status of the protec tive field and the status of the output signal switching...

Page 49: ...Result OK 1 After download or importing does the checksum of the Flexi Soft project match one of the check sums provided in Pre configured project files page 26 Yes No 2 1 If the Timing Set Selection...

Page 50: ...the material Expected result safe state Yes No 5 3 If the Timing Set Selection func tion is used Are n times configured for Ttermina tion Yes No 6 Is the clock period of the upper clock generator func...

Page 51: ...hat results in a time shorter than 10 min Yes No 9 2 If the Timing Set Selection func tion is used Are n counter function blocks in the Max time monitoring network configured for the maximum dura tion...

Page 52: ...ico Phone 52 472 748 9451 E Mail mario garcia sick com Netherlands Phone 31 0 30 229 25 44 E Mail info sick nl New Zealand Phone 64 9 415 0459 0800 222 278 tollfree E Mail sales sick co nz Norway Phon...

Reviews: