Operating instructions Register sensors RS25
Commissioning
34
© SICK AG • Presence Detection • Subject to change without notice • 8015887
8.5
Integrating XDD file of the register sensor RS25 into the configuration
program (XDD file)
To connect Powerlink devices to the network and use configuration pro-
grams to configure them, an electronic data sheet, or XDD file, is required.
The XDD (XML Device Description) file is a standardized XML format and
corresponds to the specifications of the EPSG (Ethernet Powerlink
Standardization Group).
→
For more information on Ethernet Powerlink,
see "www.ethernet-powerlink.org".
NOTE
You can download the XDD file online from
Load the XDD file into the configuration program. For this, proceed accord-
ing to the instructions of the configuration program.
8.6
Configuration of the register sensor RS25
8.6.1
Configuration procedure without key code
→
For the description of the operating modes see Page 35, Chapter 9.
A "T
0
-Trigger" must be sent for configuration without key code.
1. Switch on the supply voltage.
2. Switch to "Oscilloscope mode".
3. Perform the teach-in for the background. Set the "Mode" parameter.
Deactivate the key code. Send a „T
0
-Trigger“.
4. Perform the teach-in for the print marks. Set the "Mode" parameter.
Send a „T
0
-Trigger“.
5. Switch to "RUN mode".
8.6.2
Configuration procedure using key code
→
For the description of the operating modes see Page 35, Chapter 9.
For configuration by key code, no "T
0
-Trigger" has to be sent.
1. Switch on the supply voltage. The system starts automatically.
2. Switch to "Oscilloscope mode".
3. Perform the teach-in for the background. Set the "Mode" parameter.
Set a "T
0
-Trigger"
4. Activate the key code and perform a teach-in for key codes.
5. Perform the teach-in for the print marks. Set the "Mode" parameter.
6. Switch to "RUN mode".
The values are updated according to the "T
0
-Trigger" setting.