NOTE
In certain cases (in the event of dust, high air humidity), it may make sense not to dis‐
connect the system plug and the safety laser scanner initially. In these cases, proceed
as follows:
1.
Disconnect the connecting cables the system plug.
2.
Unscrew screws from the bracket and remove the defective safety laser scanner
from the bracket.
3.
Move the safety laser scanner with the system plug to a clean location (e.g. office,
maintenance areas).
4.
Unscrew screws in the system plug and remove the system plug from the defective
safety laser scanner.
5.
See above for further steps.
10.4.2
Completely replacing the safety laser scanner
1.
Disconnect the connecting cables the system plug.
2.
Unscrew the fixing screws and remove the defective safety laser scanner.
3.
Mount the new safety laser scanner,
.
4.
Reconnect the connecting cables to the system plug.
5.
Configure the safety laser scanner,
.
6.
Perform commissioning again, taking particular care to conduct all of the thorough
checks described,
.
10.5
Replacing the system plug
If the system plug is damaged or defective, you must replace it.
NOTICE
Enclosure rating IP65 only applies if the safety laser scanner is closed and the system
plug is mounted.
b
Mount the system plug.
b
Close the M12 plug connector on the safety laser scanner using a male cable con‐
nector or a protective cap.
°
Tightening torque for plug connector: 0.4 Nm … 0.6 Nm.
°
Tightening torque for protective caps: 0.6 Nm … 0.7 Nm.
b
When mounting the connecting cable, ensure the seals are intact and seated cor‐
rectly.
NOTICE
If the system plug is mounted with excessive force, the contacts can break or bend.
b
Plug in the system plug carefully.
b
Do not force it.
Tool required:
•
TX10 Torx wrench
Approach
1.
Make sure that the environment is clean and free of dust and moisture (high air
humidity, fog, rain, hail, snow).
2.
Disconnect the connecting cables from the system plug.
3.
If necessary: move the safety laser scanner to a clean location.
10
MAINTENANCE
114