•
Error mode
>
Hold last value for a defined time
: If no measurement is possible,
the last valid measured value is displayed and held for the time set under
Error
suppression time
(see below). Once this time has elapsed, the set
Substitute
value in the event of an error
(see above) is displayed and held until a valid meas‐
ured value is available again.
•
Error suppression time
: It is possible to set a time for which the last valid meas‐
ured value is displayed and held if the error mode
Hold last value for a defined
time
(see above) is activated.
>
Measurement
>
>
Default settings
>
>
Action in case of incorrect measurements
>
Parameter
Factory setting
Substitute value in the event of an error:
-3,276.8 m ... +3,276.7 m
+3,276.7 m
Error mode:
User-defined values
Hold last value
Hold last value for a defined time
✓
-
-
Error suppression time:
0001 ms ... 9,999 ms
1 ms
8.4
I/O interface
8.4.1
Q1 output
The Q1 output is purely a switching output. In addition, the output serves as a commu‐
nication line for bidirectional data transmission when using the IO-Link interface.
The Q1 output of the OD 1000 provides the following switching modes:
•
DtO, distance to object (1-point), one switching point
•
Window, two switching points
•
ObSB, object between sensor (device) and background, one switching point
•
Alarm (only in
Advanced
user level)
•
Signal level warning (only in
Advanced
user level)
•
Edge height change (only in
Advanced
user level)
The switching modes are explained in the subsequent chapters.
8.4.1.1
Notes on the measuring and setting functions
The following functions can be set independently from each other on both outputs
depending on the selected output function.
Delay mode
Delay mode is used to output the output state change with a time delay or as a short
switching pulse (1 shot).
OPERATION VIA DISPLAY
8
8019642/ZJW1/2017-04-03 | SICK
O P E R A T I N G I N S T R U C T I O N S | OD1000
37
Subject to change without notice