A report shows the settings and data of a device. You have the option of saving and
archiving these data as a PDF.
Report
When you open the
Report
dialog box, the Safety Designer creates a report. If you click
on
Update
after making changes to the configuration, you will receive an updated report.
Compiling a report
You compose the contents of a report individually:
1.
Select the contents of the report under
Settings for reports
.
✓
Safety Designer creates a report with the selected contents.
Complementary information
National and international standards promote or recommend specific data and the
person responsible for it. The required data are included in the report.
1.
Print the report.
2.
Write down the responsible person on the report.
3.
Archive the report.
7.20
Service
7.20.1
Device restart
If you have problems with the device, you can restart the device or subsections of the
device (safety function, connections, additional functions).
Restarting safety function
•
The fastest type of restart
•
Serious faults remain, even if the cause has been rectified (for example a locking
state because of a supply voltage which is too low).
•
Communication with the device remains intact (connections for configuration,
safety function and data not relating to safety).
•
Communication beyond the device is not impaired.
Restarting safety function and connections
•
The device’s function is also re-established after serious faults if the cause has
been rectified.
•
Communication with the device is interrupted (connections for configuration,
safety function and data not relating to safety). The device sets up communication
again automatically after restarting.
•
Communication beyond the device is not impaired.
Restarting device completely
•
The device behaves exactly as it does when the voltage supply is switched off and
back on again.
•
The device’s function is also re-established after serious faults if the cause has
been rectified.
•
Communication with the device is interrupted (connections for configuration,
safety function and data not relating to safety).
•
Communication beyond the device is interrupted. This may also affect devices
which communicate beyond the device.
CONFIGURATION
7
8025424/1ELL/2022-01-21 | SICK
O P E R A T I N G I N S T R U C T I O N S | microScan3 Pro I/O
145