O P E R AT I N G I N S T R U C T I O N S | L F P C U B I C
8019918 /ZJA6/ 2017-07-20 | S I C K A G
Subject to change without notice
4 3
8
OPERATION
8.4.13
Setting the offset
This setting makes it possible to indicate the level value on the display in relation to
the tank bottom instead of the end of the probe. The actual container level is then
indicated on the display.
Configuration
1.
Log in to expert mode; see
.
2.
Set the offset in the EXPRT-Config-Offset menu (0 mm … +3,000 mm).
O
L
IA
IAE
M
Fig. 8:
LFP Cubic
1
Level
2
QALOW/ QAHIGH
SPx/RPx
FHx/FI x
Can be set only in this zone
O: Offset
L: Probe length
M: Measurement length
IA: Inactive area at process connection
IAE: Inactive area at probe end
Note:
If the offset parameter is changed, the SPx/RPx/FLx/FHx/QALOW/QAHIGH parameters
are automatically adjusted.