COMMISSIONING
7
Commissioning
7.1
Quick commissioning (with factory settings)
Quick commissioning is used in applications under reference conditions
The following rules apply:
•
Use in metallic containers or immersion/bypass pipes
•
Use in plastic container with a coaxial tube, see
•
The liquid to be measured has a DK value of > 5, see
Commissioning
1. Mount the sensor in accordance with the installation conditions, see
.
2. The container must be empty and/or the level must be at least 200 mm below the
end of the probe.
3.
Log in to expert mode, see
4. After mounting, launch the AutCal menu item.
•
Press and hold the Set pushbutton for at least 3 seconds.
•
Use the Set pushbutton to confirm the AutCal menu item and then
use it again to confirm the “OK?” confirmation prompt.
•
The AutCal function is confirmed with !CalOK.
5.
Configure outputs, see
“8.2 Configuring the switching outputs”.
Note:
If the AutCal function has been confirmed with !NoSig, relaunch AutCal.
If problems occur during commissioning, see
.
7.2
Advanced commissioning
Advanced commissioning is required when quick commissioning is not sufficient or if
one of the following situations applies:
•
The liquid to be measured has a DK value of < 5, see
•
There are tank components which can interfere with the measurement signal
(in the case of the LFP Cubic).
•
In the event of significant ripples in the surface of the liquid.
•
If there are variations in the installation conditions, see
.