OUT
Standard
OUT
Low
7.
Press the Mode button.
7.6.12
Setting pushbutton lock
This function can be used to define to what extent the device is locked when the key
lock is triggered (
see "Activating or deactivating the button lock", page 28
Level 1 (L1): All entry functions are locked (pushbuttons and multifunctional input).
Level 2 (L2): All pushbutton entry functions are locked, only external multifunctional
input functional.
1.
Press and hold the Mode button for 2 s. The Configuration operating mode is
active.
2.
Use the plus or minus button to select Pro.
OUT
3.
Press the Mode button.
4.
Use the plus or minus button to select LocL.
OUT
5.
Press the Mode button. The preset value flashes.
OUT
6.
Use the plus or minus button to select L1 (level 1) or L2 (level 2).
OUT
Level 1 (standard)
OUT
Level 2
7.
Press the Mode button.
7.6.13
Storing or loading a parameter set (job)
Stored parameter sets (jobs) make it possible to permanently save and flexibly manage
specific application parameters (e.g., teach process, etc.) in the device for certain
marks or applications.
1.
Press and hold the Mode button for 2 s. The Configuration operating mode is
active.
2.
Use the plus or minus button to select Pro.
OUT
3.
Press the Mode button.
7
OPERATION
36