6.8.4
Pressurized enclosure system setting for Enclosure GMS815P-PS-3G
Pressurized enclosure system used: Gönnheimer F840
F840S parameters
Setting
Purging:
Yes
Purging method:
Auto no
Output function A1:
Ex-protection OK
Output function A2:
Ex-protection OK
[1]
[1] Options: Signal pressure. alarm
A1 control direction A1:
Normally open (no)
A2 control direction A1:
Normally open (no)
Purge time:
7.5 minutes
Volume:
No value
Minimum pre-purging pressure:
7 mbar
Minimum pressure in operation:
0.8 mbar
Maximum pressure during operation:
15 mbar