Commissioning and parameterization
4.3.2.2
Changing the field bus address for the Profibus module
The Profibus DP interface module is set to field bus address 126 at the factory. The
following steps are then necessary:
Check in directory “Configuration / I/O Configuration“ (
module (selection field “Interface module” is set to “Profibus DP”.
Switch to directory “Configuration / I/O Configuration / Interface Module“ and enter the
new address in field “Fieldbus address” (field “Profibus DP Configuration”).
Fig. 81
Directory “Configuration / I/O Configuration / Interface Module“
NOTICE:
Query via Interface Profibus
When connecting different sensors (e.g. FL200 and VICOTEC450) to one
MCU, a maximum of 5 connected sensors can be read out via Profibus. In
this case, up to 2 measured values can be read out for each sensor.
When connecting 6 to 8 sensors to one MCU, reading out the measured
values via Profibus is only possible when all sensors are of the same type
(e.g. 6 x FL200). Only the main measured value can be read out.
The query of all measured values of a sensor is only possible with single
sensor configuration (connection of a FL200 to a MCU).