Ethernet gateways
Step 3:
Edit the message command as follows:
– Configuration: Select
CIP Generic
. The
Class
describes the object.
Class 72
is for
Full Data Set Transfer
.
Instance 1
and
Attribute 1
determine the data type which in
this case is
Data Set 1
(see Tab. 42). As
Destination
the “WhatIWant” tag must be
chosen.
– Communication: The message has to contain the
Path
to the gateway. In this
example the path is 10.4.209.51.
5.2.8
TCP/IP configuration interface
See section 5.1.1 “TCP/IP configuration interface” on page 32.
5.2.9
Ethernet TCP/IP socket interface
See section 5.1.2 “Ethernet TCP/IP socket interface” on page 37.
Fig. 33: Explicit messaging —
Message configuration
Fig. 34: Explicit messaging —
Communication configuration