Table 115: Valid sequence for muting sensor input signals with sequence monitoring
Direction detection
Valid sequence for muting sensor input signals
Forward
A1 before A2 before B1 before B2
Backward
B2 before B1 before A2 before A1
Deviations from the sequence result in a muting error, which is indicated at the
Muting
error
output. This applies both to the sequence of activation (muting sensor signal
inputs switch from 0 to 1) and to deactivation (muting sensor signal inputs switch from
1 to 0).
Complementary information
•
If there are objects in the area of the muting sensors during the first logic cycle
and therefore one or more muting sensor signal inputs are set to 1, this gener‐
ates a muting error. The signaling of the error state at the
Muting error
output is
suppressed if the
BWS
input = 1. Before a new valid muting cycle can be executed,
this error must be reset.
•
The muting times have an accuracy of ± 10 ms (evaluation plus logic execution
time).
Further topics
•
"Safety notes for muting applications", page 18
7.6.2.7.3
Cross muting V1
Overview
A1
A2
Figure 48: Muting with a sensor pair arranged crosswise (A1 / A2)
Principle of operation
Table 116: Inputs
Input
Description
ESPE
Data type: Boolean
The input must be connected to the electro-sensitive protective device.
A1
A2
Data type: Boolean
Signal from the muting sensor
Override
(optional)
Data type: Boolean
Band signal
(optional)
Data type: Boolean
7
CONFIGURATION
98
O P E R A T I N G I N S T R U C T I O N S | Flexi Compact