8.3.4
Defining the switching window for the distance value
NOTE
The procedure for configuring the Q1 and Q2 digital outputs is identical. The configura‐
tion is illustrated on switching output Q1.
The switching state is active if the distance output value is between switching point SP1
and switching point SP2.
Switching points SP1 and SP2 respectively designate the distance value at which the
switching event is triggered (
see "Switching functions", page 16
).
The values of the switching points refer to the output distance value = measurement
direction x measured distance value + distance offset.
Parameter
Factory setting
Switching point 1:
-4500 m to 4500 m
10 m
Switching point 2:
-4500 m to 4500 m
20 m
8.3.5
Defining the switching window hysteresis for the distance value
NOTE
The procedure for configuring the Q1 and Q2 digital outputs is identical. The configura‐
tion is illustrated on switching output Q1.
Unwanted switching can be prevented by entering a hysteresis if the determined
distance value fluctuates around the set switching points (
).
The switching hysteresis for the “Window” switching function is the same for both SP1
and SP2 window limits.
Parameter
Factory setting
Hysteresis:
0 m to 1500 m
0.1 m
REFERENCE
8
8024560/1A19/2021-06-30 | SICK
O P E R A T I N G I N S T R U C T I O N S | DT1000 PROFIBUS DP and DL1000 PROFIBUS DP
73
Subject to change without notice