O P E R AT I N G I N S T R U C T I O N S | C F P C U B I C
8021989 / 2017-10-20 | SICK AG
Subject to change without notice
4 1
10
OVERVIEW OF PARAMETERS
10
Overview of parameters
Parameter
Description
Menu for switching
outputs
Based on example:
Q1-Lvl
Note:
The switching output designation changes according to
the selected process variable to be output – in this case:
Lvl (Level).
Mode1
Switching point output mode.
Output:
The switching output is used as output.
Input:
The switching output is used as input for an external
signal.
Proc1
Note:
Can only be selected
for Mode1 / Output
Switching output process parameters:
Level, temperature, or status
The corresponding switching point is marked with a refer-
ence to the selected parameter. Example: Q1-Lvl.
Out1
Switching function, switching output.
SP1
RP1
Switching point, switching output (SPx > RPx).
Reset switching point, switching output
Note: Not displayed if the switching output is used to out-
put the status (Proc1/Status) or if window is selected as
the output function.
FH1
FL1
Upper threshold (high) window function, switching output
(FHx > FLx)
Lower threshold (low) window function, switching output
Note:
Not displayed if the switching output is used to output the
status (Proc1/Status) or if hysteresis is selected as the
output function.
Pol1
Switching output property:
Normally open – no
Normally closed – nc
SimQ1
“8.5.9 Testing the configuration”.
Typ1
Switching output execution:
PNP = Switching output in PNP circuit
NPN = Switching output in NPN circuit
Q1-Drv = Switching output executed in push/pull function
Menu for analog outputs
Based on example:
Qa-Lvl
“8.4 Configuration of analog outputs”.
QaProc
Analog output process parameters:
Level, temperature.
QaTyp
Analog output output signal:
4 to 20 mA, 0 to 10 V or automated.