D-PRO Protection relay Technical Manual
Type:
Alarm
Measuring:
IB0-IB1-IB2
Phase current low part
Iaux
or
Itor
Auxiliary current or toroid current (51N)
Related parameters:
P.0101
Genset phases number
P.0102
Genset nominal voltage
P.0351
Curve selection (51 Protection)
P.0352
Maximum current threshold
P.0353
Maximum current delay
P.0354
Curve selection (51N Protection)
P.0355
Neutral maximum current threshold
P.0356
Neutral maximum current delay
P.0357
Curve selection (51V Protection)
P.0358
Maximum current threshold (% restrained overcurrent)
P.0359
Maximum current delay (% restrained overcurrent)
To disable:
P.0353=0; P.0356=0; P.0359=0
The parameters P.0351
– P.0354 – P.0357 allow to choose the curve to use for the protection
among the following:
•
0 = SICES
– Extremely inverse
•
1 = IEC
– Extremely inverse
•
2 = IEC
– Very inverse
•
3 = ANSI
– Extremely inverse (not implemented yet)
Current threshold reduction
Genset voltage (% nom)
40%
Cu
rr
e
n
t t
h
re
sh
o
ld
20%
60%
80%
100%
120%
0%
0%
40%
20%
60%
80%
100%
120%