D-PRO Protection relay Technical Manual
NOTE: the termination must be always enabled, unless the connection proceeds to
other devices and the controller is not one of the two ends.
Use the parameters of the menu 7 (in particular the parameters P.0700) to set the the proper
address of the controller (NOTE: DST4602 supports up to two D-PRO protection relays
simultaneously).
5.
SI.MO.NE is a centralized system for the collection of data: these data can be checked through a
WEB interface. The D-PRO protection relays can communicate with the SI.MO.NE system by the
Ethernet port. You must carry out the following configuration
Parameter
Name
Default
P.0530
Enabling connection and sending data to Si.Mo.Ne.
0-No
P.0531
Si.Mo.Ne primary server - IP address or name
P.0532
Si.Mo.Ne primary server port
0
P.0533
Si.Mo.Ne secondary server - IP Address or name
P.0534
Si.Mo.Ne secondary server port
0
P.0535
Data sending time with engine running
900
P.0536
Data sending time with engine stopped
3600
P.0537
“Keep Alive Network” data sending time
0
P.0539
Communication events
00
P.0542
Type of generator voltages
0
P.0581
Permanent Coordinates - Latitude (+=North, -=South).
P.0582
Permanent Coordinates - Longitude (+=East, -=West).
These parameters can be modified by the BoardPrg3xx program and by the web service in the
proper configuration page of the device. In detail:
If the parameter P.0530
is set to “1-Yes”, you enable the data sending to the “Si.Mo.Ne.”
server.
The parameter P.0531 configures the IP address or the name o
f the “Si.Mo.Ne.” primary
server, while the parameter P.0533 configures the secondary one. It is possible to set the
IP address in text format or the server name in full (e.g. “Simone.sices.eu”), which will be
converted by the controller in IP address, using the DNS server (properly configured or
automatic on GPRS). It is possible to disable the connection to the primary/secondary
server by setting the empty string.
The parameter P.0532
configures the port of the “Si.Mo.Ne.” primary server, while the
parameter P.0534 configures the secondary one. By setting the port address to zero, the
connection to the primary/secondary server is disabled. The standard port is 53052 (verify
with SICES).
The parameter P.0535 configures the time interval to send periodic data to the server
when the genset is running.
The parameter P.0536 configures the time interval to send periodic data to the server
when the genset is stopped.
The parameter P.0537 configures the time interval in minutes to send the special data
“Keep Alive Network”, used to signal a minimum activity to the server.
The parameter P.0539 configures in which cases the device must carry out the
spontaneous sending of the communication events to the server:
Bit
Value P.0539
Description
0
1
For alarms.
1
2
For warnings.
2
4
3
8
4
16
5
32
6
64