Power available for use by each output terminal and receptacle are as show below.
Use is possible up to the kVA as shown below.
1-phase 120-V receptacle
1-phase 240/120-V
receptacle
1-phase, 3-wire
output terminal
CON1 CON2 CON3 CON4 CON5 CON6 CON7
Total
U-W
36/ [18]
36/ [18]
U-N/G
18/ [9]
36/ [18]
W-N/G
18/ [9]
2.4
2.4
2.4
2.4
7.2
7.2
7.2
36/ [18]
* Figures in brackets are used when set to 480 V.
< NOTE >
If using a single-phase 120 V (between output terminals U-N/G and W-N/G), connect an
equivalent load between U-N/G and W-N/G.
If using a single-phase three-wire output terminal simultaneously with a receptacle output, make
sure that currents passing through each phase is less than the rated current of this generator.
If using at the three-phase 480-V setting, the output voltage of the single-phase three-wire type is
single-phase 240/120 V, which is the same as the three-phase 240-V setting. Accordingly, care
must be taken to not draw an excessive load as the available power is only one half.
U
W
N/G
U
-W
W-N/G
U
-N/G
Load
CON1
Load
CON3
Load
CON2
Load
CON4
CON5
Load
CON6
Load
CON7
Load