37
Starter Switch
1-Phase
Breaker
3-Phase
Breaker
3-P 208V
3-P 480V
3-P 240V
Push
Padlock Hole
9-2. 208/240/480V Switching Selection
Turn the three-phase and single-phase breakers on the operation panel to OFF and stop
operation.
Turn the lever of the voltage selector switch to the desired output setting.
Three-phase 208/240/480 V power is output to the three-phase output terminal. Refer to
section “
7-2. Connecting Load Cables
”.
Start the engine and turn the three-phase breaker to ON to transmit power to the
three-phase output terminal.
< Note >
If using at the three-phase 480 V setting, the output voltage of the single-phase three-wire
type is single-phase 240/120 V, which is the same as the three-phase 208/240 V setting.
Accordingly, care must be taken to not draw an excessive load as the available power is only
one half.
WARNING : ELECTRIC SHOCK
If performing any electric voltage switching, turn all breakers to OFF and stop
operation.
Lock the generator using a padlock so that no one except for designated operators
can operate switches.
CAUTION : PROPERTY DAMAGE
Check that the voltages of the generator output setting, output terminal connection
and load power source are consistent.
1
2
3
4
1