Protection parameter group 06
PARAMETER DESCRIPTION 191
5.7.9 Output short circuit protection function
Turn on output short circuit protection function.
Parameter
Name
Default Setting Range
Content
06-14
P.287
SCP Short circuit
protection function
1
0
Off
1
When output side is short, inverter stops and alarms SCP.
Output short circuit protection selection
If 06-14(P.287) is set to 0, output side short circuit protection function will be off.
If 06-14(P.287)=1, output short circuit protection is on, and when a short circuit on the output side is detected,
inverter “SCP” alarm will trigger.
5.7.10 PTC protection selection
Set how inverter will operate after PTC detection.
Parameter
Name
Default Setting Range
Content
06-15
P.533
PTC alarm action
0
0
Alarm and continue to run
1
Alarm and decelerate to stop
2
Alarm and stop freely
3
No alarm
06-16
P.534
Percentage of PTC
level
0.0%
0
Off
0.1%~100.0%
Action level of PTC function, 100% corresponds to
maximum analog input.
PTC level
Set analog input terminal 2-5/4-5/3-5 (02-00
(P.500)
~02-02(P.504)) to 11 (positive temperature coefficient
thermistor (PTC) input value). This parameter is defined as action level of PTC function, and 100% corresponds to
maximum analog input value
U
V
W
M
10
5
SA3
R=2kΩ
PTC Electronic input wiring diagram
2
10kΩ
Setting
Setting