Basic parameter group 01
PARAMETER DESCRIPTION 102
5.2.1 Limiting the output frequency
Output frequency can be limited. Fix the output frequency at the upper and lower limits.
Parameter
Name
Default Setting Range
Content
01-00
P.1
Maximum frequency
120.00Hz
0.00~
01-02(P.18)Hz
55K/75KF and below
60.00Hz
75K/90KF and above
01-01
P.2
Minimum frequency
0.00Hz
0~120.00Hz
Output minimum frequency
01-02
P.18
High-speed maximum
frequency
120.00Hz
01-00(P.1)~
650.00Hz
Set when
need inverter
to run over 120Hz
Maximum frequency, high-speed maximum frequency
The “maximum frequency” and the “high-speed maximum frequency” are interrelated:
1.
If the target frequency upper limit is set below 01-00(P.1), use 01-00(P.1) as the maximum frequency;
2.
If the target frequency
upper limit is between 120~650Hz, use 01-02(P.18) as the maximum frequency.
If 01-00(P.1)< 01-01(P.2), the steady output frequency will be fix at 01-00(P.1) value.
When setting the target frequency in PU mode, the frequency set value cannot exceed the value of 01-00 (P.1).
Minimum frequency
If the target frequency ≤ 01-01(P.2), the steady output frequency equals to = 01-01(P.2).
If 01-01(P.2)< target frequency ≤ 01-00(P.1)/(01-02(P.18)), the steady output frequency equals to target
frequency.
01-00(P.1)/
01-02(P.18)
01-01(P.2)
Output
frequency
(
Hz
)
Target frequency
(Hz)
5.2.2 Base frequency, base voltage
Use this function to adjust the inverter outputs (voltage, frequency) to match with the motor rating.
Parameter
Name
Default Setting Range
Content
01-03
P.3
Base frequency
50.00Hz
0.00~650.00Hz
50Hz system (00-24=1)
60.00Hz
60Hz system (00-24=0)
01-04
P.19
Base voltage
99999
0~1000.0V
Set base voltage according to motor rating.
99999
Base voltage is equal to power source voltage.
Setting
Setting