Basic Parameter Group 01
PARAMETER DESCRIPTION 61
5.2.1 Limiting the output frequency
Output frequency can be limited. Fix the output frequency at the upper and lower limits.
Parameter
Name
Default
Setting Range
Content
01-00
P.1
Maximum frequency
120.00Hz
0.00~01-02
(P.18)Hz
--
01-01
P.2
Minimum frequency
0.00Hz
0~120.00Hz
Output minimum frequency
01-02
P.18
High-speed maximum
frequency
120.00Hz
01-00(P.1)~
599.00Hz
Set when need inverter to run over 120Hz
Maximum frequency, high-speed maximum frequency
The “maximum frequency” and the “high-speed maximum frequency” are interrelated:
1.
If the target frequency upper limit is set below 01-00(P.1), use 01-00(P.1) as the maximum frequency;
2.
If the target frequency upper limit is above 01-00(P.1), use 01-02(P.18) as the maximum frequency.
If 01-00(P.1)< 01-01(P.2), the steady output frequency will be fix at 01-00(P.1) value.
When setting the target frequency in PU mode, the frequency set value cannot exceed the value of 01-00(P.1).
Minimum frequency
If the target frequency≤01-01(P.2), the steady output frequency equals to = 01-01(P.2).
If 01-01(P.2)<target frequency≤01-00(P.1)/(01-02(P.18))
, the steady output frequency equals to target frequency.
01-00(P.1)
/01-02(P.18)
01-01(P.2)
Steady
output
frequency
(
Hz
)
Target
frequency
(
Hz
)
Setting
Setting