System parameter group 00
PARAMETER DESCRIPTION 52
5.1.5 Speed display
In “monitoring output frequency” mode, the screen displays corresponding machine speed.
Parameter
Name
Default
Setting Range
Content
00-08
P.37
Speed display
0.0
0
Display output frequency(not mechanical speed)
0.1~5000.0
When 00-09(P.259)=1
1~50000
When 00-09(P.259)=0
00-09
P.259
Speed display unit
selection
1
0
Speed display unit is 1
1
Speed display unit is 0.1
Speed display
The setting value of 00-08(P.37) is the speed of motor when output frequency is 60Hz.
For example:
1.
If the transmitting belt speed is 950 m/minute when the inverter output frequency is 60Hz, set 00-08(P.37) =
950.
2.
After setting, in the keypad “output frequency monitor mode” , the screen will display the speed of the
transmitting belt.
Note: The machine speed on the screen is the theoretical value calculated proportionately by the inverter output
frequency and the setting value of 00-08(P.37). So there’s minute discrepancy between the displayed machine
speed and the actual one.