142
5.6.
Torque mode parameter setting and operation
(1) Apply power to the servo drive
After applying power to the servo drive, please switch off the DI SON signal, the servo drive
display shows “U(Torque command voltage)” 2 seconds later automatically.
(2) Test operation
Use JOG operation to confirm if the servo is running normally.
(3) Parameter setting
After wiring for torque control mode, you need to set below parameters to perform basic torque
control and speed limit.
Parameter
Name
Setting
value
Content
PA01(Note1)
Control mode option
□□□4
Torque control mode
PC05
Internal speed limit 1
1000
Set to 1000 rpm
PC06
Internal speed limit 2
1500
Set to 1500 rpm
PC07
Internal speed limit 3
2000
Set to 2000 rpm
PC01
Acceleration time constant
1000
Set to 1000ms
PC02
Deceleration time constant
500
Set to 500ms
PC03
S-curve
acceleration/deceleration
time constant
0
N/A
P15
Digital input filter time
□□□2
External terminal filter
time constant is 4ms
PA05
Internal torque limit 1
50
Maximum torque 50% as
a limit
(4) SERVO ON
Below is the procedure to perform SERVO ON.
(a)Apply control power to servo motor.
(b)Turn on the servo on signal(SON) (SON-SG is short-circuited).
Servo is ready to run when SON is ON, and servo motor will not be locked(SERVO LOCK).
(c) LSP and LSN function is invalid.
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...