TM 20/20MPI, Rev (5) April 2017
Troubleshooting
51
8.5.2
False Alarm or Warning Indication
➣
To identify the false alarm or warning indication:
1
Disconnect the power supply from the system and check the internal
wiring.
2
Reconnect the power supply and wait approximately 60 seconds. If the
indication remains, the unit requires service.
8.5.3
RS-485 Communications Network
Using the RS-485 network capability of the IR3 detector and control
software, you can connect up to 32 detectors in an addressable system with
only 4 wires (2 for power and 2 for communication). Using repeaters, the
number of detectors can be much larger (32 detectors for each repeater) up
to 247 on the same 4 wires. When using the RS-485 network, you can read
each detector status (FAULT, WARNING, ALARM) and to initiate a BIT for
each detector individually.
For more details, contact SPECTREX.
Summary of Contents for 20/20MPI
Page 2: ...www acornfiresecurity com www acornfiresecurity com...
Page 12: ...www acornfiresecurity com www acornfiresecurity com...
Page 14: ...www acornfiresecurity com www acornfiresecurity com...
Page 18: ...www acornfiresecurity com www acornfiresecurity com...
Page 24: ...www acornfiresecurity com www acornfiresecurity com...
Page 32: ...www acornfiresecurity com www acornfiresecurity com...
Page 36: ...www acornfiresecurity com www acornfiresecurity com...
Page 48: ...www acornfiresecurity com www acornfiresecurity com...
Page 52: ...www acornfiresecurity com www acornfiresecurity com...
Page 53: ...Appendix 53 Appendix www acornfiresecurity com www acornfiresecurity com...
Page 54: ...www acornfiresecurity com www acornfiresecurity com...
Page 58: ...www acornfiresecurity com www acornfiresecurity com...