ELECTRICAL OUTPUT AND THERMAL CHARACTERISTICS 

 

Table-1. Electrical characteristics at standard test conditions (STC:irradiance of 1000 W/m

2

, AM 1.5 spectrum, and a cell temperature of 25°C (77°F))

Model

name

Max imum

Power

(Pmax )

Power

Selection

Open-Curcuit

Voltage

(Voc/)

Short-Circuit

Current

(Isc)

Voltage at point

of max . Power

(Vmpp)

Current at point

of max . Power

(Impp)

Max imum

system voltage

(UL/IEC)

Over-Current

Protection

Application

Class

Max imum series

configuration(*)

Fire

performance

(UL1703)

NU-SA285

285W

+5% /-0%

39.3V

9.45A

31.8V

8.97A

1,000V

20A

A

20

type 2

NU-SA290

290W

+5% /-0%

39.5V

9.50A

32.2V

9.01A

1,000V

20A

A

20

type 2

NU-SA295

295W

+5% /-0%

39.7V

9.55A

32.5V

9.08A

1,000V

20A

A

20

type 2

NU-SA300

300W

+5% /-0%

39.9V

9.64A

32.6V

9.19A

1,000V

20A

A

20

type 2

NU-SC340

340W

+5% /-0%

46.5V

9.45A

38.2V

8.90A

1,000V

20A

A

17

type 2

NU-SC345

345W

+5% /-0%

46.7V

9.50A

38.4V

9.00A

1,000V

20A

A

17

type 2

NU-SC350

350W

+5% /-0%

46.9V

9.60A

38.5V

9.09A

1,000V

20A

A

17

type 2

NU-SC355

355W

+5% /-0%

47.0V

9.69A

38.7V

9.17A

1,000V

20A

A

17

type 2

NU-SC360

360W

+5% /-0%

47.2V

9.79A

38.9V

9.26A

1,000V

20A

A

17

type 2

ND-RB270

270W

+5% /-0%

38.4V

9.18A

30.9V

8.73A

1,000V

20A

A

21

type 2

ND-RB275

275W

+5% /-0%

38.5V

9.25A

31.1V

8.84A

1,000V

20A

A

21

type 2

note: Power mesurement tolerance: ±3 %  /

 

Rated electrical characteristics of Isc, Voc, are within 

±

10 percent of the indicated values.

 

Under normal conditions, a photovoltaic module is likely to experience conditions that produce more current and/or voltage than reported at Standard Test 

Conditions.  Accordingly,  the  values  of  Isc  and  Voc  marked  on  the  modules  listed  above  should  be  multiplied  by  a  factor  of  1.25  when  determining 
component voltage ratings, conductor ampacities, fuse sizes and size of controls connected to the module output. 

( for US market )

 

Refer to Sec. 690-8 of the National Electric Code for an additional multiplying factor of 125 percent (80 percent de-rating) which may be applicable. 

 
Application Class 

This module is rated as “Application class A” according to IEC61730.  
“Application  class  A”  means:  General  access,  hazardous  voltage, 

hazardous  power  applications;  Modules  rated  for  use  in  this  application 
class may be used in systems operating at greater than 50V DC or 240W, 
where  general  contact  access  is  anticipated.  Modules  qualified  as 
“Application  class  A”  according  to  IEC  61730  are  considered  to  meet  the 
requirements for safety class II. 

 
FIRE RATING 

This module is rated as “Fire safety class C” according to IEC61730, and 

"class E" in accordance with EN13501-1. 

 

( for US market )

 

 

Any module mounting system has limitations on inclination required 
to maintain a specific System Fire Class Rating  

 

The fire rating of a SHARP PV module is valid only when mounted in 
the manner specified in this manual.  

 

The  module  is  considered  to  be  in  compliance  with  UL1703  only 
when  the  module  is  mounted  in  the  manner  specified  by  the 
mounting instructions of this manual.  

 

A  module  with  exposed  conductive  parts  is  considered  to  be  in 
compliance  with  UL1703  only  when  it  is  electrically  grounded  in 
accordance  with  the  instructions  presented  in  this  manual  and  the 
requirements  of  the  National  Electrical  Code  for  UL  listed  products 
only.  

 

Any  module  without  a  frame  (laminate)  shall  not  be  considered  in 
compliance  with  the  requirements  of  UL1703  unless  the  module  is 
mounted with hardware that has been tested and evaluated with the 
module  under  this  standard  or  via  a  field  inspection  certifying  that 
the installed module complies with the requirements

 

of UL1703. 

 

Review  the  related  UL  description  files  when  checking  the  fire 
protection rank of the BOM concerned 

 

 

Summary of Contents for NU-SA Series

Page 1: ...se the lower edge of the module frame to deform Take necessary measures e g snow stopper to avoid possible damage 14 Periodically remove any overhanging snow and or ice from the module framework as it may cause deformation of the module frame GENERAL INSTRUCTIONS 1 INTRODUCTION Thank you for choosing SHARP photovoltaic PV module This Installation Manual contains essential information for the elect...

Page 2: ...ent for US market only 16 When installing PV modules in a readily accessible location the National Electrical Code NEC 690 33 requires installing the additional locking sleeve Multi Contact part PV SSH4 on the connector Note that this sleeve is not included with the module This requirement is for circuits operating in excess of 30 volts nominal maximum system voltage for DC or 30 volts for AC circ...

Page 3: ...igure 1 when connecting the modules to a battery or to other modules If not connected correctly the bypass diode s could be destroyed Maximum series configuration please refer to Table 1 This value is calculated under the condition of Voc at 40 C Maximum parallel configuration Parallel connection of each string shall be conducted with following two options Any other parallel connections are prohib...

Page 4: ...re mounted on should be rigid SHARP PV modules are designed to ensure optimal electrical performance under the condition that they are mounted on rigid support structures Deformation of support structure may damage PV module with its electric performance When mounting the module on structure ensure that no corner has a displacement of more than 2mm 0 08in per every 1000mm 39 37in of the diagonal f...

Page 5: ... fuse sizes and size of controls connected to the module output for US market Refer to Sec 690 8 of the National Electric Code for an additional multiplying factor of 125 percent 80 percent de rating which may be applicable Application Class This module is rated as Application class A according to IEC61730 Application class A means General access hazardous voltage hazardous power applications Modu...

Reviews: