Sharp NU-SA Series Installation Manual Download Page 4

SIM425-002 

 

 

 

 

4

 

conductivity or for use as grounding devices and should be used only 
for  maintaining  mechanical  connections  and  holding  electrical 
grounding  devices  in  the  proper  position  for  electrical  conductivity. 
Such devices, where supplied with the module and evaluated through 
the requirements in UL1703, may be used for grounding connections 
in accordance with the instructions provided with the module. 

 

Grounding Using Existing Ground Hole (Figure 4, 1954381-2) 

 

The  grounding  clip  (SolKlip  grounding  Clip  Assemblies  1954381-2,  Tyco 
electronics corp., E69905) assembly consists of a slider, base and #8-32 or 
#10-32  screw(Material;  stainless  steel)  and  hex  nut  (Material;  chromate 
treatment carbon steel). 

1.    Place  the  grounding  onto  the  frame,  making  sure  that  the  screw 

straddles the grounding hole. 

2.  Thread the hex nut onto the end of the screw, then using a 3/8” or 

5/16”  wrench,  tighten  the  nut.  Recommended  torque  is  between 
2.3(21) and 2.8 Nm (25lbf.in.). 

3.    Insert  the  grounding  wire  into  the  wire  slot.  Press  down  on  both 

ends of the wire (the wire slot will cause the wire to form a slight 
curve). The grounding cables can be insulated with green colored 
insulation  or  insulated  with  green  with  yellow  stripe(s)  insulation. 
The conductor grounding cables should be 12 AWG (Insulated for 

90

°

C (194

°

F) Min.). 

4.    Manually,  or  using  channel  lock  pliers,  push  the  slider  over  the 

base until it covers the base. This will terminate the wire. 

 

Figure 4. Tyco electronics corp. 1954381-2 

1.Wire slot (available for 0.006 to 0.025in

2

 cable), 2.Silder, 3.Bolt, 4.Base, 5.Nut 

Please contact “Tyco electronics corp.” about detail information of “1954381-2”. 

 

. MOUNTING 

Please  make  sure  that  all  the  information  described  in  the  installation 

manual  is  still  valid  and  proper  for  your  installation.  The  approved  way  to 
mount  SHARP  PV  modules  to  a  support  structure  is  described  in  this 
INSTALLATION  MANUAL.  Although  SHARP  does  not  specify  or  warrant 
frame  clips  or  clamps,  using  frame  clips  (not  provided)  or  clamps  (not 
provided)  is  possible  when  they  are  designed  for  PV  modules  and  with 

minimum  dimensions  on  the  sides  of  the  module  in  accordance  with  the 
instructions  and  drawings  provided.  If  using  frame  clips  or  clamps,  the 
modules  should  be  fixed  rigidly  and  there  shall  be  no  damage  to  the 
modules by deforming mounting structure against design load.  
The SHARP module guaranty may be void if customer-selected frame clips 
are  improper  or  inadequate  for  module  properties  (including  strength  or 
material)  or  installation.  Note  that  if  metal  clips  are  used,  there  must  be  a 
path  to  ground  from  the  clips,  (for  instance,  using  star  washers  in  the  clip 
hardware set). 

Please  review  the  descriptions  and  drawings  carefully;  not  mounting  the 

modules according to one of these methods may void your guaranty. These 
mounting  methods  are  designed  to  allow  module  loading  of  2400Pa.  the 
module  has  passed  a  snow  load  test  of  5400Pa  according  to 
IEC61215.Support  structures  that  PV  modules  are  mounted  on  should  be 
rigid.  SHARP  PV  modules  are  designed  to  ensure  optimal  electrical 
performance  under  the  condition  that  they  are  mounted  on  rigid  support 
structures.  Deformation  of  support  structure  may  damage  PV  module  with 
its  electric  performance.  When  mounting  the  module  on  structure,  ensure 
that  no  corner  has  a  displacement  of  more  than  2mm  (0.08in)  per  every 
1000mm (39.37in) of the diagonal. 
 

( for US market ) 

 

The modules have been evaluated by UL according to UL 1703 for 
maximum positive or negative design loading of 30lbs.ft

2

 

A  clearance  of  at  least  4.5in  (recommended)  is  provided  between 
modules frame and the surface of the wall or roof. If other mounting 
means are employed this may affect the UL Listing or the fire class 
ratings. 

 

8. MAINTENANCE 

SHARP  PV  modules  are  designed  for  long  life  and  require  very  little 

maintenance.  If  the  angle  of  the  PV  module  is  5  degrees  or  more,  normal 
rainfall  is  usually  sufficient  to  keep  the  module  glass  surface  clean  under 
most weather conditions. If dirt build-up becomes excessive, clean the glass 
surface only with a soft cloth using water. If cleaning the back of the module 
is  required,  take  utmost  care  not  to  damage  the  back  side  materials.  In 
order  to  ensure  proper  operation  of  the  system,  please  check  all  wiring 
connections and the condition of the wire insulation periodically. 

 

9. DISPOSAL  

Dispose photovoltaic modules properly. For Information 
about  the  proper  disposal,  contact  your  local  recycling 
site.

 

 

 
 

 

INSTALLATION MANUAL -PHOTOVOLTAIC MODULES-

 

 

1. INSTALLATION 

Please  review  the  descriptions  and  drawings  carefully;  not  mounting  the 

modules according to one of these methods may void your guaranty. These 
mounting  methods  are  basically  designed  to  allow  module  loading  of 
±2400Pa (50lbs.ft

2

). 

 

( for US market ) 

 

The modules have  been  evaluated  by UL  according to UL  1703 for 
maximum positive or negative design loading of 30lbs.ft

2

 

 

Mounting Using Clips: Clamping on Longer Frame (Figure2) 

The  modules  can  be  mounted  using  clips  (clamps)  designed  for  solar 

modules as defined in the following Figures. Note that the mounting clips 
should meet the required dimensions as defined in the Figure1. Note that 
the 

CLIP CENTER POSITION (e)

 is important as specified in the Figure2. 

The module must be supported on the array system and should overlap 
the  array  rail  by  at  least  10mm  (0.39in).  The  array  rails  (see  pointillist 
image,  row  or  vertical  row)  must  support  the  bottom  of  the  frames  and 
must be continuous piece (no breaks in the rail).  

 

 
 
 
 
 

2. ELECTRICAL INSTALLATION INSTRUCTION 

Refer to “6. ELECTRICAL INSTALLATION”  

   

CONNECTOR requirement: 

 

Multi-Contact AG (MC4 series: PV-KST4, PV-KBT4) 
Keep all electriacal CONNECTORS clean & dry before connecting. 

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Figure2. Clamping on longer Frame 

NU-SA***:  207mm (8.2in) < e < 330mm (12.9in) 
NU-SC***:  250mm (9.9in) < e < 400mm (15.7in) 
ND-RB***:  207mm (8.2in) < e < 330mm (12.9in) 
e : span from module corner to clip center 

 
 
 

Figure1. clips( clamps) requirement 
*available to all FRAME section 
   1) Clip: Al alloy, 3mm (0.12in) Min. thickness 
   2) Catch length (50mm (2.0in) Min.) 
   3) Covering depth (7mm (0.28in) Min. on the frame) 
   4) Supporting depth (10mm (0.39in) Min.) 
   5) Frame 
   6) Array rail  
      (applicable to parallel or crossed mounting) 

Summary of Contents for NU-SA Series

Page 1: ...se the lower edge of the module frame to deform Take necessary measures e g snow stopper to avoid possible damage 14 Periodically remove any overhanging snow and or ice from the module framework as it may cause deformation of the module frame GENERAL INSTRUCTIONS 1 INTRODUCTION Thank you for choosing SHARP photovoltaic PV module This Installation Manual contains essential information for the elect...

Page 2: ...ent for US market only 16 When installing PV modules in a readily accessible location the National Electrical Code NEC 690 33 requires installing the additional locking sleeve Multi Contact part PV SSH4 on the connector Note that this sleeve is not included with the module This requirement is for circuits operating in excess of 30 volts nominal maximum system voltage for DC or 30 volts for AC circ...

Page 3: ...igure 1 when connecting the modules to a battery or to other modules If not connected correctly the bypass diode s could be destroyed Maximum series configuration please refer to Table 1 This value is calculated under the condition of Voc at 40 C Maximum parallel configuration Parallel connection of each string shall be conducted with following two options Any other parallel connections are prohib...

Page 4: ...re mounted on should be rigid SHARP PV modules are designed to ensure optimal electrical performance under the condition that they are mounted on rigid support structures Deformation of support structure may damage PV module with its electric performance When mounting the module on structure ensure that no corner has a displacement of more than 2mm 0 08in per every 1000mm 39 37in of the diagonal f...

Page 5: ... fuse sizes and size of controls connected to the module output for US market Refer to Sec 690 8 of the National Electric Code for an additional multiplying factor of 125 percent 80 percent de rating which may be applicable Application Class This module is rated as Application class A according to IEC61730 Application class A means General access hazardous voltage hazardous power applications Modu...

Reviews: