Sharp ND-U230C1 Installation And User Manual Download Page 4

Ver. 2.0U Dec. 4, 2008 

 

 

- 4 -                                                                    Installation Manual for PV modules 

B) MODULE SPECIFIC INSTRUCTIONS 

 

MECHANICAL INSTALLATION 

There are several approved ways to mount these Sharp PV modules to 

a support structure. They may be mounted either using the bolt holes 

provided or using frame clamps (not provided). Inter-module type or 
end-type clamps must be designed for PV modules and have minimum 

dimensions shown in Figure 5 on the long sides of the module in 

accordance with the instructions below and drawings provided. Sharp 

does not warranty frame clamps. The Sharp module warranty may be 
void if customer-selected frame clamps are improper or inadequate 

with respect to properties (including strength or material) or installation. 

Note that if metal clamps are used, there must be a path to ground 

from the clamps, (for instance, by using star washers in the hardware 

set). Please review the descriptions below and drawings carefully; not 

mounting the modules according to one of these methods may void 

your warranty. Additionally, UL has tested and listed these modules for 

mounting using either bolts or clamps. Mounting with clamps is 

considered to be equivalent to mounting with bolts and is acceptable 

under the same conditions as bolt mounting. These mounting methods 

are designed to allow module loading of 2400 Pa. Figure 7 and 8 gives 

indications of maximum point loads for an installed array. 
 

Mounting Using Frame Bolt Holes (Figures 6 , 9 & 10) 

The modules may be fastened to a support using the bolt holes in the 

bottom of the frame at location “C”, as shown in Figure 9 and 10 (back 
view of the module) and Figure 6 (mounting detail). The module should 

be fastened with four (4) M8 (5/16”) bolts. 

 

Mounting Using Clamps on Long Edge of Module: Long Edge 

Parallel to Array Rails (Figures 5 , 11 & 12) 

The modules may be mounted using clamps designed for solar 

modules as shown in Figures 5 . Note that the clamp positions are 

important – the clamp centerlines must be between 9.3” (235 mm) and 

19.4” (495 mm) regarding ND series as shown in Figure 11, and 8.3” 

(210mm) and 18.5” (470mm) regarding NT/NE series as shown in 

Figure 12 from the end of the module. The module must be supported 

along the length of the long edge, and should overlap the array rail by 

at least 0.4” (10 mm). Note that the mounting clamps should meet the 
minimum dimensions (catch width of 0.2” (5 mm), thickness of 0.13” 

(3.3 mm) and length of 1.5” (38 mm)) as shown in Figure 5. The array 

rails must support the bottom of the modules and must be a continuous 

piece (no unspliced breaks in the rail). 

 

Mounting Using Clamps on Long Edge of Module: Long Edge 
Perpendicular to Array Rails (Figures 5 , 13 & 14) 

The modules may also be mounted using clamps on the long sides of 
the module when the array rails are perpendicular to the long sides, as 

shown in Figure 13 and 14. The clamp centerlines must be between 

9.3” (235 mm) and 19.4” (495 mm) regarding ND series as shown in 

Figure 13, and 8.3” (210mm) and 18.5” (470mm) regarding NT/NE 
series as shown in Figure 14 from the ends of the module. The module 

must be supported along the length of the long edge, and should 

overlap the array rail by at least 0.4” (10 mm). Note that the mounting 

clamps should meet the minimum dimensions (catch width of 0.2” (5 
mm) , thickness of 0.13” (3.3 mm) and length of 1.5” (38 mm) shown in 

Figure 5. The array rails must support the bottom of the modules and 

must be continuous pieces (no unspliced breaks in the rail). 

 
 

 
 
 

 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

 
 
 
 
 

 
 
 
 
 

 
 
 
 

 

10 mm Min. 
support width 

Clamp 

Rail 

Frame 

catch length 

catch length 

38 mm Min. 

5 mm Min. 

3.3 mm Min. 
thickness 

Figure 5 

 

BOLT M8 X 20 mm 

Figure 6 

Point Load carrying capability 

Figure 7 (ND series) 

Figure 5 

 

 

Figure 6 

Point Load carrying capability 

Figure 7 (ND series) 

: High (

100 kg)   

: Middle(

50 kg) 

×

: Low 

: High (

100 kg)   

: Middle(

50 kg) 

×

: Low 

Figure 8 (NT/NE series) 

Summary of Contents for ND-U230C1

Page 1: ...thal shock whether the PV modules are connected or not 4 PV modules produce electricity when sufficient sunlight or other light source illuminates the module When modules are connected in series voltage is cumulative When modules are connected in parallel current is cumulative PV systems can produce high voltage and current which could present an increased hazard and may cause serious injury or de...

Page 2: ...oves with padding in the palm and finger areas 14 Do not drop the PV module or allow objects to fall on the PV module 15 Do not lift the PV module by only one side The frame may bend Always use two hands to lift and carry the PV module on the long side of the frame 16 Some PV modules incorporate one or more support bars on the back of the module Do not mount or carry the PV module using the suppor...

Page 3: ...ions below In a connection of this type the hardware such as a star washer must score the frame surface to make positive electrical contact with the frame The ground wire must not be smaller than No 14 AWG 2 1 mm2 and should be sized according to the NEC Hardware used must be compatible with the mounting structure material to avoid galvanic corrosion If using the SHARP On Energy mounting system th...

Page 4: ...5 11 12 The modules may be mounted using clamps designed for solar modules as shown in Figures 5 Note that the clamp positions are important the clamp centerlines must be between 9 3 235 mm and 19 4 495 mm regarding ND series as shown in Figure 11 and 8 3 210mm and 18 5 470mm regarding NT NE series as shown in Figure 12 from the end of the module The module must be supported along the length of th...

Page 5: ... s Figure 12 NT NE series Figure 9 ND series u u u u Figure 12 NT NE series Figure 9 ND series Figure 10 NT NE series 8 3 210 mm g 18 5 470 mm Figure 11 ND series 9 3 235 mm e 19 4 495 mm Figure 13 ND series 9 3 235 mm s 19 4 495 mm 8 3 210 mm u 18 5 470 mm Figure 14 NT NE series ...

Page 6: ...m power Ipmax 7 66 A 7 54 A 7 48 A 7 25 A 7 04 A Maximum System Voltage 600 V 600 V 600 V 600 V 600 V Minimum Blocking diode 15 A 15 A 15 A 15 A 15 A Series Fuse 15 A 15 A 15 A 15 A 15 A NT 175UC1 NT 170UC1 NE 170UC1 NE 165UC1 Maximum Power Pmax 175 0 W 142 0 W 170 0 W 165 0 W Open Circuit Voltage Voc 44 4 V 43 2 V 43 2 V 43 1 V Short Circuit Current Isc 5 40 A 5 47 A 5 47 A 5 31 A Voltage at maxi...

Page 7: ...nship and materials and Sharp agrees that for a period of one 1 year from the date of purchase by the consumer that Sharp will at its option either repair the defect or replace the defective Product or part thereof with a new or remanufactured equivalent at no charge to the purchaser for parts or labor for the period s set forth below Limited Warranty For Power The warranty period with respect to ...

Page 8: ...improper voltage or power surges or abnormal environmental conditions such as acid rain or other pollution c the components in the construction base on which the module is mounted are defective d external corrosion mold discoloration or the like occurs e the product has been moved from its original installation f the model number or serial number of the product is altered removed or rendered illeg...

Reviews: