Doc
#
E166703
10-3
10: Using the Optional Display
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
10.3: MDSN/MDLN Specifications
Following are the display specifications and important safety information.
10.3.1: General Specifications
Electrical Specifications
Environmental Specifications
Display
Model
Rated
Input
Voltage
Input
Voltage
Limits
Voltage
Drop
Power
Consumption
In-Rush
Current
Voltage
Endurance
Insulation
Resistance
MDSN
24 V DC
(20.4 to
28.8) V DC
10 ms or
less
6.5 W or less
30 A or less 1,000 V AC
20 mA for 1 min
(between
charging and FG
terminals)
500 V DC, 10
MW or more
(between
charging and
FG terminals)
MDLN
24 V DC
(20.4 to
28.8) V DC
7 ms or
less
6.8 W or less
30 A or less 1,000 V AC
20 mA for 1 min
(between
charging and FG
terminals)
500 V DC, 10
MW or more
(between
charging and
FG terminals)
MDSN
MDLN
Physical Environment
Surrounding Air
Temperature
(0 to 50) °C/(32 to122) °F
(0 to 50) °C/(32 to 122) °F
Storage Temperature (-20 to +60) °C/(-4 to +140) °F)
(-20 to +60) °C/(-4 to +140) °F
Surrounding Air and
Storage Humidity
85% RH (Wet bulb temperature:
39 °C/102.2 °F or less - no
condensation.)
85% RH (Wet bulb temperature:
39 °C/102.2 °F) or less - no
condensation.)
Dust
0.1 mg/m
3
/10
-7
oz/ft
3
or less
(non-conductive levels)
0.1 mg/m
3
/10
-7
oz/ft
3
or less
(non-conductive levels)
Pollution Degree
For use in Pollution Degree 2
environment
For use in Pollution Degree 2
environment
Corrosive Gases
Free of corrosive gases
Free of corrosive gases
Atmospheric Pressure
(Operating Altitude)
800 to 1,114 hPa (2,000 m/ 6,561
ft or lower)
800 to 1,114 hPa (2,000 m /6,561 ft
or lower)
Mechan
ical En
vi
ronmen
t
Vibration Resistance
EN61131-2 compliant
5 to 9 Hz Single amplitude: 3.5 mm/
0.14 in.
EN61131-2 compliant
5 to 9 Hz Single amplitude: 3.5 mm/
0.14 in.