8.2.1: Modbus/TCP to RTU Bridge Setup Default Settings
1) Network/IP Settings:
Network Mode................................Wired Only
IP Address......................................10.0.0.1
Default Gateway.............................--- not set ---
Netmask.........................................255.255.255.0
2) Serial & Mode Settings:
Protocol...........................................Modbus/RTU,Slave<s> attached
Serial Interface.................................57600,8,N,1,RS232,CH1
3) Modem/Configurable Pin Settings:
CP0..! Defaults <In> Wired CP1..! GPIO <In> CP2..! GPIO <In>
CP3..! GPIO <In> CP4..! GPIO <In> CP5..! GPIO <In>
CP6..! GPIO <In> CP7..! GPIO <In> CP8..! GPIO <In>
CP9..! GPIO <In> CP10.! GPIO <In>
RTS Output ......................................Fixed High/Active
4) Advanced Modbus Protocol settings:
Slave Addr/Unit Id Source..................Modbus/TCP header
Modbus Serial Broadcasts...................Disabled (Id=0 auto-mapped to 1)
MB/TCP Exception Codes....................Yes (return 00AH and 00BH)
Char, Message Timeout.......................00050msec, 05000msec
6) WLAN Settings:
WLAN...............................................Disabled, network:LTRX_IBSS
Topology..........................................AdHoc, Country: US, Channel: 11