Shark 100BT Quick Start Manual Download Page 1

     

Doc

#    

E145753   V.1.04     

          

             QS - 1

                        Shark® 100BT Quickstart

Electro 

Industries/GaugeTech

The Leader In Power Monitoring and Smart Grid Solutions

Electro 

Industries/GaugeTech

The Leader In Power Monitoring and Smart Grid Solutions

Shark® 100BT Quickstart Guide

Mechanical Installation

Installation Steps: 

Slide top of groove of meter onto DIN Rail. Press gently until the meter clicks into 

place. If mounting with DIN Rail provided, use Black Rubber Stoppers (also provided) shown above.  
To remove meter, pull down on Release clip. 

 

Electrical Installation: 

Select diagram for your application.

NOTE: 

Other wiring configurations are available. See the full Manual on the enclosed CD.

5.02”

 

 [12.75cm] 

 

3.25” 

   [8.26cm]

Ic       Ib       Ia 

HI HI HI 

LO 

LO 

LO 

3.52”

 [ 8.90cm]

0.62”
[1.61cm]

   [12.10cm]

4.78"

   [2.31cm]

0.91" 

4.16”

    [10.60cm]

DIN Installation

                                                 

Release clip

100BT

Dimensions

DIN Rail with black 

lc

HI

LO

lb

HI

LO

la

HI

LO

Earth Ground

L(+)

Power 
Supply
Connection

N(-)

L(+)

GND

N(-)

Vref

Va

Vb

Vc

LINE

LOAD

CT 
Shorting
Block

 FUSES
3 x 0.1A

 FUSE

3A

C

C

B

B

A

A

N

N

lc

HI

LO

lb

HI

LO

la

HI

LO

Earth Ground

Earth Ground

L(+)

Power 
Supply
Connection

N(-)

L(+)

GND

N(-)

Vref

Va

Vb

Vc

LINE

LOAD

CT 
Shorting
Block

 FUSES
3 x 0.1A

 FUSE

3A

C

C

B

B

A

A

N

N

lc

HI

LO

lb

HI

LO

la

HI

LO

Earth Ground

Earth Ground

L(+)

Power 
Supply
Connection

N(-)

L(+)

GND

N(-)

Vref

Va

Vb

Vc

LINE

LOAD

CT 
Shorting
Block

 FUSES
2 x 0.1A

 FUSE

3A

C

C

B

B

A

A

WYE direct, 3 
phase, 4 wire

Delta direct, 3 
phase, 3 wire

lc

HI

LO

lb

HI

LO

la

HI

LO

Earth Ground

L(+)

Power 
Supply
Connection

N(-)

L(+)

GND

N(-)

Vref

Va

Vb

Vc

LINE

LOAD

CT 
Shorting
Block

 FUSES
3 x 0.1A

 FUSE

3A

C

C

B

B

A

A

WYE with PTs, 
3 phase, 4 wire

Delta with PTs, 3 
phase, 3 wire

Summary of Contents for 100BT

Page 1: ...I LO LO LO 3 52 8 90cm 0 62 1 61cm 12 10cm 4 78 2 31cm 0 91 4 16 10 60cm DINInstallation Release clip 100BT Dimensions DIN Rail with black lc HI LO lb HI LO la HI LO Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 3 x 0 1A FUSE 3A C C B B A A N N lc HI LO lb HI LO la HI LO Earth Ground Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc L...

Page 2: ... address so that it will communicate on your Network 1 Select Start Control Panel Network Connections You will see the screen shown on the right 2 Right click on the Local Area Connection you will use to communicate with the meter and select Properties You will see the screen below on the left 3 Select Internet Protocol TCP IP and click the Properties button You will see the screen below on the ri...

Page 3: ...age shown below on the right 11 Click in the IP Address field and change the meter s factory set IP address 10 0 0 1 to an IP address in the same subnet as your Network Contact your System Administrator if you are unsure of the address to use 12 Click OK at the bottom of the webpage 13 Click Activate Configuration on the left side of the webpage to display the screen shown on the right 14 Click Co...

Page 4: ... PT Numerator x PT Multiplier Current Full Scale CT Numerator x CT Multiplier IMPORTANT Specify Primary and Secondary Voltage in Full Scale NOT Ratios Example CT Settings 200 5 Amps set the Ct n value as 200 Ct S value as 1 800 5Amps set the Ct n value as 800 Ct S value as 1 2000 5 Amps set the Ct n value as 2000 Ct S value as 1 10 000 5 Amps set the Ct n value as 1000 Ct S value as 10 Example PT ...