Operating Instructions – MOVITRAC® B
7
List of faults (F00 – F113)
Service / list of faults
04
Brake chopper
Immediate switch-
off with inhibit
•
Too much regenerative power
•
Extend deceleration ramps
•
Braking resistor circuit interrupted •
Check supply cable to braking
resistor
•
Short circuit in the braking resis-
tor circuit
•
Eliminate short circuit
•
Braking resistance too high
•
Check technical data of braking
resistor
•
Brake chopper defective
•
Replace MOVITRAC
®
B
•
Ground fault
•
Eliminate ground fault
06
Line phase fail-
ure
Immediate switch-
off with inhibit (only
with 3-phase
inverter)
•
Phase failure
•
Check the line cable
•
Line voltage too low
•
Check the line voltage
07
DC link over-
voltage
Immediate switch-
off with inhibit
•
DC link voltage too high
•
Extend deceleration ramps
•
Check supply cable to braking
resistor
•
Check technical data of braking
resistor
•
Ground fault
•
Eliminate ground fault
08
Speed monitor-
ing
Immediate switch-
off with inhibit
Current controller works at the set
limit due to:
–
•
Mechanical overload
•
Reduce load
•
Check current limitation
•
Extend deceleration ramps
•
Increase the set deceleration time
P501
1)
•
Phase failure in supply system
•
Check line phases
•
Phase failure in motor
•
Check motor cable and motor
•
Maximum speed for VFC operat-
ing modes exceeded
•
Reduce maximum speed
09
Startup
Immediate switch-
off with inhibit
•
Inverter not started yet
•
Start up the inverter
•
Unknown motor selected
•
Select another motor
10
IPOS-ILLOP
Stop with inhibit
With IPOS only
•
Wrong command during program
execution
•
Check the program
•
Incorrect conditions during pro-
gram execution
•
Check program run
•
Function does not exist / is not
implemented in the inverter
•
Use another function
11
Overtempera-
ture
Stop with inhibit
•
Thermal overload of inverter
•
Reduce load and/or ensure ade-
quate cooling
•
If a braking resistor is integrated
in the heat sink: Install braking
resistor externally
17
–
24
System error
Immediate switch-
off with inhibit
•
Inverter electronics is faulty, pos-
sibly due to EMC
•
Check grounding and shielding
and improve, if necessary
•
Contact SEW Service for advice if
this error reoccurs.
25
EEPROM
Stop with inhibit
•
Error while accessing EEPROM
•
Restore factory settings, perform
reset and reset parameters.
•
Consult SEW Service if the error
reoccurs
26
External termi-
nal
Programmable
•
Read in external fault signal via
programmable input.
•
Eliminate respective cause;
reprogram terminal if necessary
No.
Designation
Response
Possible cause
Measures