Drive Technology \ Drive Automation \ System Integration \ Services

Compact Operating Instructions

MOVITRAC

®

 LTP-B

Edition 03/2021

26879778/EN

Summary of Contents for MOVITRAC LTP-B

Page 1: ...26879778_0321 Drive Technology Drive Automation System Integration Services Compact Operating Instructions MOVITRAC LTP B Edition 03 2021 26879778 EN...

Page 2: ...SEW EURODRIVE Driving the world...

Page 3: ...s 7 2 1 Preliminary information 7 2 2 Duties of the user 7 2 3 Target group 7 2 4 Network security and access protection 8 2 5 Designated use 8 2 6 Functional safety technology 9 2 7 Transport 9 2 8 I...

Page 4: ...he grading and meaning of the signal words for safety notes Signal word Meaning Consequences if disregarded DANGER Imminent hazard Severe or fatal injuries WARNING Possible dangerous situation Severe...

Page 5: ...alues In this document a period is used to indicate the decimal separator Example 30 5 kg 1 4 Rights to claim under limited warranty Read the information in this documentation This is essential for fa...

Page 6: ...ing Instructions MOVITRAC LTP B 6 1 8 Copyright notice 2021 SEW EURODRIVE All rights reserved Unauthorized reproduction modifica tion distribution or any other use of the whole or any part of this doc...

Page 7: ...ons who work on the product pay attention to the following regula tions conditions documentation and information National and regional safety and accident prevention regulations Warning and safety sig...

Page 8: ...o adapt electronic drive technology components to the particulars of the machinery within wide limits There is a risk that a change of pa rameters that cannot be detected externally may result in unex...

Page 9: ...an WEEE Directive 2012 19 EU You may use options and accessories from SEW EURODRIVE exclusively in connec tion with products from SEW EURODRIVE 2 6 Functional safety technology The product must not pe...

Page 10: ...with impermissibly high mechanical vibration and shock loads in excess of the regulations stipulated in EN 61800 5 1 Use at an elevation of more than 3800 m above sea level The product can be used at...

Page 11: ...ve measure for the product Type of energy transfer Preventive measure Direct power supply Ground connection 2 9 3 Regenerative operation The drive is operated as a generator due to the kinetic energy...

Page 12: ...product from the voltage supply do not touch any live compo nents or power connections because capacitors might still be charged Observe the following minimum switch off time 10 minutes Observe the c...

Page 13: ...P B 0015 2B1 4 00 60 Hz Product name MCLTP MOVITRAC LTP B Version B Version status of the device series Recommended motor power 0015 0015 1 5 kW Connection voltage 2 2 200 240 V 5 380 480 V 6 500 600...

Page 14: ...14 Design 00 00 Standard IP20 housing 10 IP55 NEMA 12K housing 15 IP55 NEMA 12K housing for operation on IT systems 30 IP66 NEMA 4X housing without switch 40 IP66 NEMA 4X housing with switch xH High...

Page 15: ...urce that is usually limited by fuses or motor protection switches The inverter has the degree of protection IP20 For a higher IP degree of protec tion a suitable enclosure or the IP55 NEMA 12K or the...

Page 16: ...must be deactivated IP20 devices On sizes 2 and 3 unscrew the EMC screw and the VAR screw on the side of the device 1 2 3034074379 1 EMC screw 2 VAR screw L3 N L2 L L1 Internal EMC Filter Internal Sur...

Page 17: ...s carry a high DC voltage approx DC 900 V during nominal operation Severe or fatal injuries Before removing the supply cable disconnect the inverter from the power supply and wait at least 10 minutes...

Page 18: ...tect the braking resistor with a bimetallic relay and set the tripping current IF of the respective braking resistor The flatpack resistors have internal thermal overload protection fuse cannot be re...

Page 19: ...r or inverter Connection ex ample of the differ ent temperature sensors and their parameterization TF temperature sensor Bimetallic switch TH KTY84 PT1000 24 VIO DI 1 DI 2 DI 3 10 V AI 1 DI 4 0 V AO 1...

Page 20: ...of the external use of terminals 2 3 and 6 the internally fitted switches and potentiometers can be deacti vated The procedure is described in chapter P0 00 configuration parameters for IP66 NEMA 4X d...

Page 21: ...0 V 10 0 V PTC th 0 20 mA 4 20 mA 20 4 mA KTY84 PT1000 digital 0 24 V 11 AO 2 DO 2 Analog output 2 10 bit Digital input 2 Analog 0 10 V 10 0 V 0 20 mA 20 0 mA 4 20 mA 20 4 mA Digital 0 24 V max 20 mA...

Page 22: ...2 NO contact 4 1 6 Communication socket RJ45 NOTICE Voltage at socket not suitable for PCs Damage to PC when connected directly to RJ45 communication socket Use the engineering adapters as described i...

Page 23: ...ers with degree of protection IP66 NEMA 4X already have openings for supply system motor and control cables 230 V 0 75 5 5 kW 400 V 0 75 11 kW 575 V 0 75 15 kW The following inverters with degree of p...

Page 24: ...V W M 3 MOVITRAC LT BR 3 1 ND LT 2 F16 K10 5 9007217635508875 1 Line contactor between supply system and inverter 2 Brake 3 Main switch only for device design IP66 NEMA 4X housing with switch MC LTP...

Page 25: ...17 18 1 3 2 BMK V DC BMV BM V 3 2 3 white red bue red white blue Cut off in the AC circuit Cut off in the DC and AC circuits 18475023883 1 Power supply of the brake rectifier switched simultaneously v...

Page 26: ...up of the inverter without additional devices Standard keypad MOVITRAC LT 4 5 6 1 2 3 18014401443146379 1 6 digit 7 segment display 4 Navigate button 2 Start button 5 Up button 3 Stop Reset button 6 D...

Page 27: ...state The parameter edit menu can only be accessed by pressing the Navigate key 4 To switch between the menu for changing parameters and real time display oper ating speed operating current Keep the k...

Page 28: ...t setting is 50 The setting range can be changed by the user between 5 100 using the F2 function key B As soon as a key on the keypad is pressed the brightness imme diately increases to 100 again Info...

Page 29: ...l value when changing a pa rameter value Up Down keys The parameter is set to the lowest value When changing P1 01 50 0 is displayed Press the Up Down keys 0 0 is now displayed Changing indi vidual di...

Page 30: ...ings Firmware update manual and automatic Export inverter parameters to Microsoft Word Monitor the state of the inputs and outputs and the motor Control inverter manual mode Scope Connection to LT She...

Page 31: ...erating Instructions MOVITRAC LTP B 31 Connection to LT Shell via Bluetooth parameter module MOVITRAC LT L1 L L2 N L3 BR U V W 1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 LTP B 1 9007216440559755 1 Pa...

Page 32: ...are available in MOVITOOLS MotionStudio Monitor upload and download parameters Save parameter settings Monitor the state of inputs outputs and of the motor Connection to MOVITOOLS MotionStudio The co...

Page 33: ...DHP 11B X31 X32 X33 X30 ON 20 21 7 8 9007216441033995 1 USB A B cable 5 Terminating connector 120 2 USB11A or USM21A 6 Cable splitter 3 RJ10 to RJ10 cable 7 USB A B cable 4 RJ45 cable with open end 8...

Page 34: ...hanging the control mode in P4 01 when the motor is cold You can also start auto tuning manually via the parameter P4 02 at any time 5 3 Startup for motors WARNING If parameter P4 02 is set to 1 auto...

Page 35: ...uto Tune 2 34 6 In case of insufficient control performance the control behavior can be optimized via the parameter P7 10 5 3 3 Startup with asynchronous motors or torque motors with VFC torque contro...

Page 36: ...and deceleration ramps using P1 03 and P1 04 5 Start the automatic motor measurement procedure Auto Tune as described in chapter Auto Tune 2 34 6 Check the magnetizing current P0 14 at half nominal sp...

Page 37: ...in chapter Auto Tune 2 34 6 Adjust the boost parameters A default setting is P7 14 10 P7 15 10 7 In case of insufficient control performance the control behavior can be optimized via the parameter P7...

Page 38: ...08 Rated current of the motor P1 09 Rated frequency of the motor P1 10 Rated speed of the motor P1 14 201 Extended parameter menu P4 01 8 BLDC speed control P4 05 Power factor 3 Set the maximum speed...

Page 39: ...is connected The functions are limited see also chapter 24 V backup mode 6 1 2 Operating state of the inverter The following table shows the messages of the status for an enabled inverter You can tog...

Page 40: ...L Main Loss Phase failure or supply voltage outside of specification FirE Fire mode Fire mode emergency mode activated The message is displayed al ternately with the current operating state dELAy t De...

Page 41: ...ults The power rating of the motor corresponds with the power rating of the connected inverter dAtA E 19 0x62 0x1013 Internal memory error DSP Contact SEW EURODRIVE Service dAtA F 17 0x62 0x1011 Inter...

Page 42: ...or during refer ence travel Check reference cams Check limit switch connection Check reference travel type setting and the parameters required for it Inhibit STO safety circuit open Check to see if th...

Page 43: ...in P1 11 Set a longer run up time in P1 03 Disconnect the motor from the inverter Enable the in verter again If this fault occurs again check the entire system and completely replace the inverter Faul...

Page 44: ...ads mass moment of inertia or connect additional braking resistors in parallel Note the minimum resistor values for the inverter in use OF 01 60 0x1C 0x103C Internal connec tion to option module error...

Page 45: ...sed due to the heat sink temperature SP Err 31 0x0E 0x101F Speed error P6 07 The difference between the actual speed and setpoint speed is larger than the percentage value set in P6 07 This error appl...

Page 46: ...TRAC LTP B 46 Code in verter dis play Code MotionStudio in P0 13 Error code status word if Bit5 1 CANopen emergency code Meaning Measure USr PS Parameter backup successfully com pleted The parameter s...

Page 47: ......

Page 48: ...SEW EURODRIVE Driving the world SEW EURODRIVE GmbH Co KG Ernst Blickle Str 42 76646 BRUCHSAL GERMANY Tel 49 7251 75 0 Fax 49 7251 75 1970 sew sew eurodrive com www sew eurodrive com...